EA-450AG10-C10 C
46.00 kW
Defrost: None
Product code: EA-463ED7-C06 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 34,387 m³/h |
|---|---|
| Air throw | 25 m |
| External surface | 224.7 m² |
| Inner volume | 64.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 356 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 890 rpm |
| Power | 2,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 79.1 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-463ED7-C06 C | None |
|---|---|
| EA-463ED7-C06 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 17.53 | 17.40 | 17.36 | 17.39 | 17.34 | 17.25 | 17.13 | 17.38 | 18.41 | 19.92 | 19.47 | 19.31 | 19.08 | 18.74 |
| 5 | 23.11 | 23.20 | 23.34 | 23.45 | 23.46 | 23.35 | 23.17 | 23.39 | 24.82 | 26.85 | 26.19 | 25.96 | 25.64 | 25.16 |
| 6 | 28.48 | 28.98 | 29.45 | 29.87 | 30.01 | 29.96 | 29.74 | 29.94 | 31.74 | 34.30 | 33.36 | 33.00 | 32.51 | 31.77 |
| 7 | 33.57 | 34.61 | 35.39 | 36.18 | 36.60 | 36.72 | 36.60 | 36.82 | 39.02 | 42.19 | 40.98 | 40.52 | 39.86 | 38.80 |
| 8 | 38.04 | 39.58 | 41.00 | 42.30 | 43.14 | 43.64 | 43.67 | 43.96 | 46.60 | 50.43 | 49.03 | 48.47 | 47.65 | 46.31 |
| 9 | 42.06 | 44.17 | 46.11 | 47.83 | 48.99 | 49.71 | 50.07 | 50.60 | 53.74 | 58.35 | 57.04 | 56.50 | 55.67 | 54.07 |
| 10 | 45.78 | 48.53 | 51.04 | 53.24 | 54.78 | 55.75 | 56.29 | 56.92 | 60.47 | 65.66 | 64.22 | 63.60 | 62.67 | 61.08 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.45 | 15.27 | 15.22 | 15.24 | 15.22 | 15.16 | 15.09 | 15.31 | 16.27 | 17.63 | 17.27 | 17.14 | 16.95 | 16.68 |
| 5 | 20.22 | 20.19 | 20.24 | 20.35 | 20.35 | 20.27 | 20.14 | 20.32 | 21.57 | 23.35 | 22.81 | 22.61 | 22.35 | 21.96 |
| 6 | 25.06 | 25.26 | 25.50 | 25.76 | 25.81 | 25.76 | 25.60 | 25.75 | 27.30 | 29.52 | 28.74 | 28.46 | 28.05 | 27.43 |
| 7 | 29.65 | 30.22 | 30.76 | 31.27 | 31.50 | 31.52 | 31.38 | 31.50 | 33.34 | 36.05 | 35.05 | 34.67 | 34.11 | 33.20 |
| 8 | 33.99 | 35.02 | 35.82 | 36.65 | 37.13 | 37.31 | 37.26 | 37.42 | 39.64 | 42.89 | 41.68 | 41.15 | 40.39 | 39.12 |
| 9 | 37.80 | 39.30 | 40.67 | 41.92 | 42.75 | 43.19 | 43.27 | 43.50 | 46.10 | 49.90 | 48.48 | 47.85 | 46.91 | 45.31 |
| 10 | 41.35 | 43.31 | 45.11 | 46.73 | 47.80 | 48.49 | 48.86 | 49.33 | 52.37 | 56.83 | 55.40 | 54.67 | 53.56 | 51.61 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 64.223 | 55.398 |
| SC2 | 0 | 8 | 43.958 | 37.419 |
| SC3 | -18 | 7 | 36.393 | 31.388 |
| SC4 | -25 | 6 | 29.450 | 25.501 |
| SC5 | -34 | 6 | 28.626 | 25.135 |
| A | 3615 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 3235 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 3615 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.