EA-463GG4-C13 C
141.75 kW
Defrost: None
Product code: EA-563FG4-C08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 64,354 m³/h |
|---|---|
| Air throw | 39 m |
| External surface | 835.3 m² |
| Inner volume | 166.7 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 769 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FG4-C08 C | None |
|---|---|
| EA-563FG4-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 56.66 | 57.39 | 58.02 | 58.81 | 59.13 | 59.08 | 58.72 | 60.23 | 64.20 | 69.74 | 68.50 | 68.10 | 67.57 | 66.52 |
| 5 | 72.12 | 74.19 | 76.05 | 77.63 | 78.38 | 78.45 | 77.94 | 79.18 | 84.19 | 91.33 | 89.12 | 88.36 | 87.28 | 85.71 |
| 6 | 86.58 | 89.84 | 93.19 | 96.04 | 97.67 | 98.26 | 97.92 | 99.30 | 105.42 | 114.26 | 111.04 | 109.81 | 108.01 | 105.13 |
| 7 | 98.71 | 103.99 | 108.82 | 113.06 | 115.84 | 117.40 | 117.85 | 119.59 | 127.05 | 138.01 | 134.08 | 132.46 | 130.02 | 126.03 |
| 8 | 109.89 | 117.01 | 123.52 | 129.19 | 133.06 | 135.31 | 136.12 | 138.04 | 146.59 | 159.17 | 155.12 | 153.41 | 150.79 | 146.37 |
| 9 | 120.08 | 129.17 | 137.53 | 144.86 | 149.99 | 153.05 | 154.41 | 156.64 | 166.33 | 180.49 | 175.99 | 173.96 | 170.84 | 165.46 |
| 10 | ≈ 129.29 | 140.46 | 150.84 | 159.98 | 166.44 | 170.65 | 172.66 | 175.30 | 186.18 | 202.00 | 197.11 | 194.78 | 191.19 | not rated |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 50.82 | 54.20 | 58.93 | 57.93 | 57.60 | 57.17 | 56.60 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 70.10 | 76.08 | not rated | not rated | not rated | not rated |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | 92.77 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | 105.95 | 109.82 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | 118.37 | 123.38 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | 130.26 | 136.57 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 197.106 | — |
| SC2 | 0 | 8 | 138.038 | — |
| SC3 | -18 | 7 | 114.333 | — |
| SC4 | -25 | 6 | 93.193 | — |
| SC5 | -34 | 6 | 87.509 | — |
| A | 5415 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| G | 1135 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.