EA-240AE4-C01 C
11.94 kW
Defrost: None
Product code: EA-630BC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,307 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 40.2 m² |
| Inner volume | 11.7 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 77 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 72.7 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-630BC6-C01 C | None |
|---|---|
| EA-630BC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.39 | 4.49 | 4.58 | 4.67 | 4.70 | 4.70 | 4.67 | 4.78 | 5.09 | 5.52 | 5.40 | 5.35 | 5.28 | 5.18 |
| 5 | 5.67 | 5.90 | 6.11 | 6.29 | 6.38 | 6.42 | 6.41 | 6.53 | 6.94 | 7.53 | 7.35 | 7.28 | 7.20 | 7.07 |
| 6 | 6.82 | 7.18 | 7.52 | 7.82 | 8.03 | 8.13 | 8.20 | 8.35 | 8.87 | 9.63 | 9.41 | 9.32 | 9.19 | 8.97 |
| 7 | 7.78 | 8.30 | 8.72 | 9.14 | 9.44 | 9.64 | 9.76 | 9.94 | 10.58 | 11.52 | 11.30 | 11.21 | 11.07 | 10.83 |
| 8 | 8.66 | 9.27 | 9.89 | 10.45 | 10.86 | 11.14 | 11.32 | 11.53 | 12.28 | 13.38 | 13.13 | 13.02 | 12.84 | 12.54 |
| 9 | ≈ 9.29 | 10.22 | 11.00 | 11.71 | 12.25 | 12.62 | 12.86 | 13.13 | 13.99 | 15.24 | 14.97 | 14.84 | 14.64 | 14.29 |
| 10 | ≈ 10.10 | 11.10 | 12.05 | 12.92 | 13.59 | 14.07 | 14.40 | 14.72 | 15.69 | 17.11 | 16.83 | 16.69 | 16.46 | 16.05 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.831 |
| SC2 | 0 | 8 | 11.533 |
| SC3 | -18 | 7 | 9.271 |
| SC4 | -25 | 6 | 7.518 |
| SC5 | -34 | 6 | 6.902 |
| A | 2557 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2557 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.