ED-240AE4-C21 C
14.85 kW
Defrost: None
Product code: ED-340AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,432 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 45.8 m² |
| Inner volume | 15.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 116 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-340AC7-C21 C | None |
|---|---|
| ED-340AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.40 | 5.36 | 5.34 | 5.34 | 5.31 | 5.26 | 5.21 | 5.26 | 5.56 | 6.00 | 5.84 | 5.79 | 5.71 | 5.59 |
| 5 | 7.19 | 7.24 | 7.31 | 7.37 | 7.37 | 7.33 | 7.27 | 7.31 | 7.75 | 8.37 | 8.14 | 8.06 | 7.95 | 7.78 |
| 6 | 8.97 | 9.17 | 9.35 | 9.49 | 9.57 | 9.58 | 9.53 | 9.58 | 10.15 | 10.96 | 10.64 | 10.53 | 10.36 | 10.11 |
| 7 | 10.62 | 10.99 | 11.34 | 11.66 | 11.84 | 11.91 | 11.90 | 11.97 | 12.69 | 13.73 | 13.35 | 13.20 | 12.98 | 12.62 |
| 8 | 12.03 | 12.56 | 13.06 | 13.51 | 13.78 | 13.99 | 14.11 | 14.28 | 15.17 | 16.49 | 16.14 | 15.98 | 15.72 | 15.30 |
| 9 | 13.33 | 14.05 | 14.65 | 15.25 | 15.68 | 15.97 | 16.15 | 16.36 | 17.39 | 18.90 | 18.53 | 18.37 | 18.13 | 17.72 |
| 10 | 14.53 | 15.38 | 16.23 | 17.00 | 17.55 | 17.94 | 18.19 | 18.45 | 19.62 | 21.34 | 20.94 | 20.76 | 20.49 | 20.03 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.941 |
| SC2 | 0 | 8 | 14.275 |
| SC3 | -18 | 7 | 11.741 |
| SC4 | -25 | 6 | 9.349 |
| SC5 | -34 | 6 | 9.026 |
| A | 2148 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 467 mm |
| E1 | 1835 mm |
| E2 | 618 mm |
| E3 | 600 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2148 mm |
|---|---|
| Width | 1210 mm |
| Height | 467 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.