EG-230BE7-C21 C
4.59 kW
Defrost: None
Product code: EG-425AC7-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,851 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 14.6 m² |
| Inner volume | 3.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 4 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 260 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 64.4 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EG-425AC7-C23 C | None |
|---|---|
| EG-425AC7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.74 | 1.74 | 1.73 | 1.74 | 1.73 | 1.72 | 1.69 | 1.73 | 1.85 | 2.00 | 1.96 | 1.94 | 1.91 | 1.88 |
| 5 | 2.30 | 2.32 | 2.35 | 2.37 | 2.38 | 2.37 | 2.34 | 2.38 | 2.52 | 2.73 | 2.65 | 2.62 | 2.59 | 2.54 |
| 6 | 2.85 | 2.91 | 2.97 | 3.03 | 3.06 | 3.06 | 3.03 | 3.07 | 3.25 | 3.52 | 3.41 | 3.36 | 3.30 | 3.20 |
| 7 | 3.33 | 3.43 | 3.54 | 3.64 | 3.70 | 3.73 | 3.74 | 3.79 | 4.02 | 4.35 | 4.21 | 4.15 | 4.07 | 3.94 |
| 8 | 3.80 | 3.94 | 4.07 | 4.21 | 4.29 | 4.35 | 4.36 | 4.41 | 4.69 | 5.09 | 4.95 | 4.90 | 4.81 | 4.67 |
| 9 | 4.22 | 4.42 | 4.61 | 4.78 | 4.89 | 4.95 | 4.98 | 5.05 | 5.36 | 5.81 | 5.66 | 5.59 | 5.49 | 5.32 |
| 10 | 4.61 | 4.87 | 5.12 | 5.33 | 5.48 | 5.57 | 5.61 | 5.68 | 6.03 | 6.54 | 6.38 | 6.30 | 6.19 | 5.98 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.381 |
| SC2 | 0 | 8 | 4.414 |
| SC3 | -18 | 7 | 3.665 |
| SC4 | -25 | 6 | 2.971 |
| SC5 | -34 | 6 | 2.862 |
| A | 2746 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 618 mm |
| E2 | 600 mm |
| E | 2435 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 2746 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.