EK-DI-263AC10-A08 C
30.70 kW
Defrost: None
Product code: EK-DI-163AI10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,103 m³/h |
|---|---|
| External surface | 132.0 m² |
| Inner volume | 54.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 285 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EK-DI-163AI10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.52 | 12.35 | 12.28 | 12.27 | 12.21 | 12.13 | 12.02 | 12.15 | 12.90 | 13.97 | 13.66 | 13.55 | 13.38 | 13.12 |
| 5 | 14.72 | 14.67 | 14.68 | 16.38 | 16.34 | 16.25 | 16.10 | 16.19 | 17.15 | 18.54 | 18.04 | 17.86 | 17.61 | 17.24 |
| 6 | 18.18 | 18.29 | 18.44 | 20.63 | 20.68 | 20.60 | 20.45 | 20.50 | 21.71 | 23.44 | 22.75 | 22.50 | 22.12 | 21.55 |
| 7 | 21.45 | 21.81 | 22.15 | 24.99 | 25.14 | 25.12 | 24.97 | 25.01 | 26.47 | 28.59 | 27.72 | 27.38 | 26.87 | 26.04 |
| 8 | 24.55 | 25.21 | 25.82 | 29.29 | 29.54 | 29.64 | 29.55 | 29.62 | 31.35 | 33.87 | 32.84 | 32.41 | 31.77 | 30.72 |
| 9 | 30.50 | 31.63 | 32.51 | 33.41 | 33.95 | 34.18 | 34.19 | 34.31 | 36.33 | 39.27 | 38.11 | 37.61 | 36.85 | 35.59 |
| 10 | 33.44 | 34.80 | 36.16 | 37.39 | 38.19 | 38.68 | 38.83 | 39.04 | 41.36 | 44.71 | 43.45 | 42.88 | 42.02 | 40.57 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.69 | 10.52 | 10.45 | 10.45 | 10.42 | 10.36 | 10.27 | 10.44 | 11.11 | 12.04 | 11.80 | 11.71 | 11.60 | 11.43 |
| 5 | 12.53 | 12.42 | 12.40 | 13.81 | 13.78 | 13.69 | 13.57 | 13.70 | 14.53 | 15.73 | 15.32 | 15.18 | 14.98 | 14.68 |
| 6 | 15.42 | 15.40 | 15.46 | 17.29 | 17.30 | 17.21 | 17.06 | 17.15 | 18.17 | 19.64 | 19.07 | 18.85 | 18.54 | 18.06 |
| 7 | 18.30 | 18.42 | 18.59 | 20.84 | 20.91 | 20.86 | 20.70 | 20.76 | 21.97 | 23.74 | 23.00 | 22.71 | 22.29 | 21.60 |
| 8 | 21.03 | 21.34 | 21.67 | 24.44 | 24.60 | 24.57 | 24.41 | 24.47 | 25.89 | 27.96 | 27.08 | 26.72 | 26.19 | 25.31 |
| 9 | 26.25 | 26.86 | 27.45 | 28.00 | 28.26 | 28.32 | 28.20 | 28.26 | 29.89 | 32.24 | 31.26 | 30.83 | 30.20 | 29.14 |
| 10 | 28.97 | 29.89 | 30.75 | 31.42 | 31.84 | 32.01 | 31.96 | 32.06 | 33.93 | 36.62 | 35.52 | 35.04 | 34.31 | 33.08 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 43.445 | 35.521 |
| SC2 | 0 | 8 | 29.622 | 24.469 |
| SC3 | -18 | 7 | 25.068 | 20.885 |
| SC4 | -25 | 6 | 18.435 | 15.464 |
| SC5 | -34 | 6 | 18.227 | 15.430 |
| A | 1725 mm |
|---|---|
| B | 1200 mm |
| C | 1150 mm |
| F | 1160 mm |
| G | 1740 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1740 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.