EK-DI-163AI10-A08 C
30.92 kW
Defrost: None
Product code: EK-DI-263AC10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 34,354 m³/h |
|---|---|
| External surface | 105.5 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 356 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EK-DI-263AC10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.74 | 11.43 | 11.24 | 11.13 | 11.01 | 10.88 | 10.76 | 10.73 | 11.34 | 12.23 | 11.90 | 11.79 | 11.62 | 11.38 |
| 5 | 14.24 | 14.02 | 13.89 | 15.35 | 15.21 | 15.03 | 14.85 | 14.78 | 15.62 | 16.82 | 16.32 | 16.14 | 15.88 | 15.49 |
| 6 | 18.01 | 17.92 | 17.90 | 19.88 | 19.79 | 19.61 | 19.40 | 19.29 | 20.38 | 21.95 | 21.26 | 21.01 | 20.65 | 20.10 |
| 7 | 21.64 | 21.79 | 21.97 | 24.60 | 24.61 | 24.49 | 24.28 | 24.17 | 25.54 | 27.51 | 26.64 | 26.32 | 25.84 | 25.11 |
| 8 | 25.10 | 25.57 | 25.92 | 29.25 | 29.45 | 29.45 | 29.33 | 29.26 | 30.93 | 33.36 | 32.34 | 31.95 | 31.37 | 30.46 |
| 9 | 31.30 | 32.16 | 33.00 | 33.80 | 34.33 | 34.50 | 34.49 | 34.49 | 36.50 | 39.42 | 38.30 | 37.85 | 37.19 | 36.12 |
| 10 | 34.40 | 35.64 | 36.79 | 37.87 | 38.58 | 39.04 | 39.30 | 39.55 | 41.98 | 45.52 | 44.38 | 43.89 | 43.16 | 41.95 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.50 | 10.22 | 10.06 | 9.98 | 9.89 | 9.80 | 9.72 | 9.71 | 10.27 | 11.09 | 10.82 | 10.72 | 10.58 | 10.38 |
| 5 | 12.68 | 12.44 | 12.31 | 13.60 | 13.49 | 13.37 | 13.22 | 13.18 | 13.94 | 15.03 | 14.62 | 14.47 | 14.26 | 13.93 |
| 6 | 16.02 | 15.85 | 15.76 | 17.50 | 17.41 | 17.28 | 17.09 | 17.03 | 18.00 | 19.40 | 18.83 | 18.62 | 18.32 | 17.86 |
| 7 | 19.28 | 19.27 | 19.32 | 21.58 | 21.54 | 21.43 | 21.24 | 21.17 | 22.38 | 24.12 | 23.40 | 23.12 | 22.73 | 22.12 |
| 8 | 22.43 | 22.64 | 22.88 | 25.70 | 25.79 | 25.75 | 25.59 | 25.52 | 26.99 | 29.11 | 28.20 | 27.87 | 27.39 | 26.61 |
| 9 | 28.26 | 28.80 | 29.24 | 29.74 | 30.00 | 30.08 | 29.99 | 29.98 | 31.69 | 34.22 | 33.24 | 32.85 | 32.27 | 31.34 |
| 10 | 31.24 | 32.08 | 32.91 | 33.72 | 34.24 | 34.46 | 34.47 | 34.50 | 36.53 | 39.49 | 38.43 | 37.99 | 37.33 | 36.26 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 44.383 | 38.429 |
| SC2 | 0 | 8 | 29.255 | 25.522 |
| SC3 | -18 | 7 | 24.622 | 21.579 |
| SC4 | -25 | 6 | 17.902 | 15.756 |
| SC5 | -34 | 6 | 18.017 | 16.001 |
| A | 3025 mm |
|---|---|
| B | 900 mm |
| C | 1150 mm |
| F | 860 mm |
| G | 1440 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3025 mm |
|---|---|
| Width | 1440 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.