Skip to Content

Blast freezer EK-DI-263AG10-A08 C

Blast freezer EK-DI-263AG10-A08 C
Illustrative photo

Producer: Karyer · Line: EK-DI (Cold Store)

Product code: EK-DI-263AG10-A08 C

Cooling capacity i
54.58 kW
Air flow
31,428 m³/h
Fin spacing
10.0 mm
Fans
2 × ⌀630 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EK-DI — EK-DI - blast freezer, cold-store (DI) design, fans inclined 45°
  • B
    Number of fans: 2 — Number of fans (one digit).
  • C
    Fan diameter: 63 — Ø630 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: G — 8 tube rows
  • F
    Fin spacing: 10 — Fin spacing about 10 mm
  • G
    Generation code: A — Generation A
  • H
    Fan data: 08 — Ø630: 400V/3Ph/50Hz, 4-pole

Data

Evaporator
Air flow 31,428 m³/h
External surface 211.1 m²
Inner volume 87.4 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 463 kg
Fans
Quantity 2
Diameter 630 mm
Speed 1,340 rpm
Power 3,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 72.0 dB(A)
Sound power 95.0 dB(A)
Energy class D
Connections
Inlet Ø42
Outlet Ø66,7
Defrost
EK-DI-263AG10-A08 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
52.164 kW
Low speed (Y)
43.926 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 22.01 21.51 21.24 21.11 20.95 20.75 20.55 20.73 21.97 23.74 23.17 22.96 22.66 22.22
5 26.27 25.90 25.71 28.50 28.31 28.04 27.73 27.84 29.48 31.83 30.97 30.66 30.23 29.59
6 32.87 32.68 32.60 36.30 36.18 35.90 35.52 35.55 37.62 40.59 39.36 38.91 38.27 37.31
7 39.25 39.39 39.64 44.37 44.38 44.13 43.74 43.72 46.24 49.88 48.30 47.71 46.84 45.48
8 45.38 45.98 46.60 52.46 52.70 52.61 52.26 52.16 55.17 59.55 57.66 56.92 55.84 54.12
9 56.89 58.18 59.22 60.34 60.91 61.03 60.81 60.85 64.37 69.49 67.37 66.49 65.24 63.18
10 62.63 64.51 66.34 68.04 69.10 69.53 69.47 69.64 73.71 79.61 77.29 76.32 74.89 72.52

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 19.06 18.62 18.40 18.32 18.22 18.09 17.94 18.18 19.31 20.92 20.49 20.32 20.08 19.73
5 22.63 22.24 22.05 24.45 24.31 24.11 23.87 24.04 25.50 27.58 26.87 26.63 26.28 25.78
6 28.18 27.89 27.80 30.91 30.79 30.57 30.25 30.35 32.14 34.71 33.70 33.33 32.81 32.01
7 33.77 33.65 33.70 37.57 37.54 37.33 36.97 37.01 39.15 42.27 40.95 40.45 39.72 38.58
8 39.15 39.30 39.59 44.38 44.46 44.28 43.93 43.93 46.45 50.14 48.54 47.90 46.98 45.48
9 49.25 49.84 50.50 51.17 51.44 51.36 51.04 51.03 53.96 58.23 56.39 55.63 54.49 52.66
10 54.75 55.83 56.91 57.79 58.28 58.39 58.16 58.23 61.59 66.45 64.41 63.54 62.25 60.11

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 77.29264.408
SC2 0 8 52.16443.926
SC3 -18 7 44.40237.581
SC4 -25 6 32.59527.795
SC5 -34 6 32.86828.143

Dimensions

Dimension drawing of EK-DI-263AG10-A08 C
Dimension drawing
Dimensions as drawn
A 3025 mm
B 1100 mm
C 1150 mm
F 1060 mm
G 1640 mm
E1 1318 mm
E 2635 mm
D IN 1 x Ø42
D OUT 1 x Ø66,7
Overall [mm]
Length 3025 mm
Width 1640 mm
Height 1150 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.