EK-DI-463AC10-A08 C
57.29 kW
Defrost: None
Product code: EK-DI-263AG10-A13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 35,473 m³/h |
|---|---|
| External surface | 211.1 m² |
| Inner volume | 87.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 467 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EK-DI-263AG10-A13 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 22.60 | 22.05 | 21.74 | 21.58 | 21.38 | 21.17 | 20.95 | 21.05 | 22.26 | 24.04 | 23.44 | 23.21 | 22.90 | 22.44 |
| 5 | 27.12 | 26.72 | 26.51 | 29.34 | 29.12 | 28.82 | 28.49 | 28.49 | 30.15 | 32.53 | 31.62 | 31.29 | 30.83 | 30.15 |
| 6 | 34.05 | 33.86 | 33.82 | 37.58 | 37.43 | 37.14 | 36.74 | 36.67 | 38.77 | 41.79 | 40.51 | 40.05 | 39.38 | 38.37 |
| 7 | 40.72 | 40.92 | 41.20 | 46.12 | 46.13 | 45.88 | 45.48 | 45.38 | 47.97 | 51.72 | 50.08 | 49.47 | 48.57 | 47.18 |
| 8 | 47.12 | 47.84 | 48.54 | 54.68 | 54.94 | 54.80 | 54.50 | 54.42 | 57.54 | 62.06 | 60.12 | 59.37 | 58.26 | 56.48 |
| 9 | 59.08 | 60.35 | 61.73 | 62.98 | 63.64 | 63.85 | 63.69 | 63.68 | 67.38 | 72.74 | 70.57 | 69.69 | 68.38 | 66.27 |
| 10 | 64.84 | 66.94 | 68.94 | 70.79 | 71.98 | 72.70 | 72.91 | 73.07 | 77.36 | 83.60 | 81.23 | 80.25 | 78.78 | 76.36 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 19.45 | 18.97 | 18.72 | 18.62 | 18.49 | 18.35 | 18.20 | 18.38 | 19.51 | 21.11 | 20.64 | 20.46 | 20.21 | 19.84 |
| 5 | 23.20 | 22.77 | 22.56 | 24.98 | 24.82 | 24.61 | 24.36 | 24.46 | 25.92 | 28.02 | 27.29 | 27.04 | 26.68 | 26.15 |
| 6 | 28.97 | 28.67 | 28.56 | 31.73 | 31.59 | 31.35 | 31.03 | 31.07 | 32.88 | 35.49 | 34.46 | 34.08 | 33.55 | 32.73 |
| 7 | 34.80 | 34.68 | 34.73 | 38.71 | 38.66 | 38.44 | 38.09 | 38.07 | 40.26 | 43.44 | 42.10 | 41.60 | 40.86 | 39.68 |
| 8 | 40.39 | 40.59 | 40.90 | 45.85 | 45.93 | 45.76 | 45.42 | 45.37 | 47.97 | 51.77 | 50.12 | 49.46 | 48.50 | 46.96 |
| 9 | 50.85 | 51.52 | 52.24 | 52.96 | 53.26 | 53.21 | 52.93 | 52.85 | 55.87 | 60.30 | 58.39 | 57.60 | 56.44 | 54.54 |
| 10 | 56.53 | 57.75 | 58.77 | 59.88 | 60.43 | 60.60 | 60.43 | 60.48 | 63.97 | 69.04 | 66.91 | 65.99 | 64.65 | 62.43 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 81.230 | 66.907 |
| SC2 | 0 | 8 | 54.417 | 45.366 |
| SC3 | -18 | 7 | 46.156 | 38.713 |
| SC4 | -25 | 6 | 33.818 | 28.555 |
| SC5 | -34 | 6 | 34.048 | 28.937 |
| A | 3025 mm |
|---|---|
| B | 1100 mm |
| C | 1150 mm |
| F | 1060 mm |
| G | 1640 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 3025 mm |
|---|---|
| Width | 1640 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.