EK-DI-263AI10-A13 C
66.57 kW
Defrost: None
Product code: EK-DI-363AE10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 49,239 m³/h |
|---|---|
| External surface | 238.1 m² |
| Inner volume | 99.8 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 614 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 5,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 97.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø80 |
| EK-DI-363AE10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 26.13 | 25.49 | 25.11 | 24.93 | 24.70 | 24.45 | 24.21 | 24.30 | 25.70 | 27.75 | 27.06 | 26.80 | 26.44 | 25.92 |
| 5 | 31.44 | 30.95 | 30.68 | 33.95 | 33.69 | 33.35 | 32.97 | 32.98 | 34.90 | 37.65 | 36.61 | 36.24 | 35.71 | 34.93 |
| 6 | 39.54 | 39.28 | 39.22 | 43.57 | 43.39 | 43.04 | 42.59 | 42.52 | 44.96 | 48.47 | 47.01 | 46.47 | 45.71 | 44.56 |
| 7 | 47.38 | 47.56 | 47.85 | 53.54 | 53.55 | 53.26 | 52.81 | 52.70 | 55.72 | 60.07 | 58.21 | 57.50 | 56.49 | 54.91 |
| 8 | 54.90 | 55.68 | 56.46 | 63.57 | 63.75 | 63.71 | 63.37 | 63.29 | 66.93 | 72.20 | 69.99 | 69.13 | 67.87 | 65.86 |
| 9 | 68.93 | 70.33 | 71.89 | 73.30 | 74.06 | 74.30 | 74.15 | 74.16 | 78.48 | 84.75 | 82.26 | 81.27 | 79.78 | 77.40 |
| 10 | 75.67 | 78.01 | 80.27 | 82.38 | 83.78 | 84.60 | 84.98 | 85.18 | 90.20 | 97.51 | 94.80 | 93.69 | 92.03 | 89.29 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 23.02 | 22.44 | 22.13 | 22.00 | 21.85 | 21.68 | 21.51 | 21.68 | 22.97 | 24.84 | 24.28 | 24.07 | 23.78 | 23.35 |
| 5 | 27.55 | 27.04 | 26.77 | 29.64 | 29.44 | 29.18 | 28.90 | 28.99 | 30.71 | 33.18 | 32.33 | 32.02 | 31.60 | 30.96 |
| 6 | 34.49 | 34.12 | 33.98 | 37.76 | 37.59 | 37.31 | 36.94 | 36.96 | 39.11 | 42.21 | 41.00 | 40.56 | 39.93 | 38.98 |
| 7 | 41.49 | 41.35 | 41.42 | 46.17 | 46.12 | 45.87 | 45.47 | 45.43 | 48.06 | 51.85 | 50.28 | 49.69 | 48.84 | 47.51 |
| 8 | 48.21 | 48.46 | 48.85 | 54.77 | 54.90 | 54.74 | 54.34 | 54.29 | 57.41 | 61.96 | 60.05 | 59.32 | 58.24 | 56.52 |
| 9 | 60.74 | 61.58 | 62.46 | 63.36 | 63.74 | 63.66 | 63.39 | 63.36 | 67.03 | 72.34 | 70.17 | 69.29 | 68.01 | 65.90 |
| 10 | 67.57 | 68.87 | 70.32 | 71.69 | 72.40 | 72.67 | 72.54 | 72.62 | 76.85 | 83.00 | 80.60 | 79.60 | 78.12 | 75.65 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 94.803 | 80.600 |
| SC2 | 0 | 8 | 63.289 | 54.285 |
| SC3 | -18 | 7 | 53.582 | 46.175 |
| SC4 | -25 | 6 | 39.215 | 33.981 |
| SC5 | -34 | 6 | 39.535 | 34.444 |
| A | 4325 mm |
|---|---|
| B | 1000 mm |
| C | 1150 mm |
| F | 960 mm |
| G | 1540 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 3935 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø80 |
| Length | 4325 mm |
|---|---|
| Width | 1540 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.