Skip to Content

Blast freezer EK-DI-363AE10-A13 C

Blast freezer EK-DI-363AE10-A13 C
Illustrative photo

Producer: Karyer · Line: EK-DI (Cold Store)

Product code: EK-DI-363AE10-A13 C

Cooling capacity i
68.78 kW
Air flow
55,131 m³/h
Fin spacing
10.0 mm
Fans
3 × ⌀630 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EK-DI — EK-DI - blast freezer, cold-store (DI) design, fans inclined 45°
  • B
    Number of fans: 3 — Number of fans (one digit).
  • C
    Fan diameter: 63 — Ø630 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: E — 6 tube rows
  • F
    Fin spacing: 10 — Fin spacing about 10 mm
  • G
    Generation code: A — Generation A
  • H
    Fan data: 13 — Ø630: 400V/3Ph/50Hz, 4-pole

Data

Evaporator
Air flow 55,131 m³/h
External surface 238.1 m²
Inner volume 99.8 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 621 kg
Fans
Quantity 3
Diameter 630 mm
Speed 1,330 rpm
Power 8,100 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 69.0 dB(A)
Sound power 93.0 dB(A)
Energy class E
Connections
Inlet Ø42
Outlet Ø80
Defrost
EK-DI-363AE10-A13 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
65.592 kW
Low speed (Y)
55.680 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 26.74 26.06 25.64 25.41 25.15 24.87 24.60 24.61 26.00 28.06 27.34 27.07 26.70 26.14
5 32.31 31.80 31.51 34.84 34.53 34.15 33.73 33.65 35.58 38.35 37.25 36.85 36.29 35.42
6 40.76 40.52 40.45 44.91 44.70 44.32 43.83 43.67 46.15 49.72 48.18 47.62 46.81 45.60
7 48.90 49.16 49.49 55.39 55.38 55.10 54.60 54.41 57.51 61.96 60.01 59.27 58.21 56.56
8 56.69 57.61 58.49 65.72 66.10 66.07 65.73 65.59 69.36 74.80 72.48 71.59 70.28 68.20
9 70.77 72.59 74.37 76.06 76.92 77.21 77.09 77.08 81.57 88.09 85.50 84.47 82.95 80.48
10 77.88 80.47 82.92 85.20 86.70 87.63 88.11 88.64 93.96 101.58 98.79 97.65 95.95 93.16

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 23.38 22.76 22.42 22.27 22.09 21.91 21.73 21.83 23.10 24.97 24.38 24.16 23.86 23.42
5 28.09 27.54 27.25 30.14 29.91 29.64 29.34 29.35 31.07 33.54 32.66 32.34 31.89 31.22
6 35.36 34.87 34.71 38.55 38.36 38.06 37.68 37.61 39.78 42.90 41.66 41.21 40.56 39.58
7 42.49 42.36 42.42 47.32 47.21 46.95 46.56 46.44 49.10 52.95 51.35 50.75 49.88 48.53
8 49.41 49.71 50.12 56.21 56.34 56.19 55.81 55.68 58.88 63.52 61.59 60.84 59.74 57.99
9 62.27 63.21 64.17 65.11 65.41 65.47 65.24 65.16 68.93 74.42 72.19 71.29 69.98 67.86
10 69.27 70.70 72.27 73.73 74.53 74.85 74.80 74.84 79.21 85.57 83.12 82.11 80.61 78.13

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 98.79283.124
SC2 0 8 65.59255.680
SC3 -18 7 55.42347.275
SC4 -25 6 40.44534.712
SC5 -34 6 40.75935.304

Dimensions

Dimension drawing of EK-DI-363AE10-A13 C
Dimension drawing
Dimensions as drawn
A 4325 mm
B 1000 mm
C 1150 mm
F 960 mm
G 1540 mm
E1 1318 mm
E2 1300 mm
E 3935 mm
D IN 1 x Ø42
D OUT 1 x Ø80
Overall [mm]
Length 4325 mm
Width 1540 mm
Height 1150 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.