EK-K-s-463BE10-B08 C
66.98 kW
Defrost: None
Product code: EK-K-b-463BE10-B29 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 59,481 m³/h |
|---|---|
| External surface | 219.7 m² |
| Inner volume | 95.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 555 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 7,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 98.0 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø54 |
| EK-K-b-463BE10-B29 C | None |
|---|---|
| EK-K-b-463BE10-B29 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | ≈ 26.19 | ≈ 25.28 | ≈ 24.73 | ≈ 24.42 | ≈ 24.11 | ≈ 23.83 | ≈ 23.56 | ≈ 23.69 | ≈ 25.06 | ≈ 27.07 | ≈ 26.42 | ≈ 26.19 | ≈ 25.87 | ≈ 25.41 |
| 5 | ≈ 32.19 | ≈ 31.26 | ≈ 30.67 | ≈ 33.66 | ≈ 33.19 | ≈ 32.68 | 32.18 | ≈ 32.32 | ≈ 34.20 | ≈ 36.86 | ≈ 35.83 | ≈ 35.45 | ≈ 34.93 | ≈ 34.15 |
| 6 | ≈ 41.22 | ≈ 40.37 | 39.83 | ≈ 43.87 | ≈ 43.31 | ≈ 42.65 | 41.92 | ≈ 41.94 | ≈ 44.34 | ≈ 47.73 | ≈ 46.24 | ≈ 45.72 | ≈ 44.99 | ≈ 43.90 |
| 7 | ≈ 50.45 | ≈ 49.83 | ≈ 49.49 | ≈ 54.71 | ≈ 54.20 | ≈ 53.47 | 52.58 | ≈ 52.49 | ≈ 55.45 | ≈ 59.64 | ≈ 57.60 | ≈ 56.87 | ≈ 55.83 | ≈ 54.28 |
| 8 | ≈ 59.42 | ≈ 59.25 | ≈ 59.28 | ≈ 65.97 | ≈ 65.61 | ≈ 64.91 | 63.92 | 63.74 | ≈ 67.30 | ≈ 72.39 | 69.77 | 68.81 | 67.42 | 65.28 |
| 9 | ≈ 75.66 | ≈ 76.17 | ≈ 76.75 | ≈ 77.32 | ≈ 77.14 | ≈ 76.62 | 75.69 | 75.46 | 79.68 | 85.74 | 82.63 | 81.42 | 79.68 | 76.92 |
| 10 | ≈ 84.75 | ≈ 85.88 | ≈ 87.26 | ≈ 88.44 | ≈ 88.82 | ≈ 88.56 | 87.76 | 87.55 | 92.47 | 99.61 | 96.07 | 94.66 | 92.59 | 89.28 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | ≈ 26.19 | ≈ 25.28 | ≈ 24.74 | ≈ 24.44 | ≈ 24.13 | ≈ 23.83 | ≈ 23.56 | ≈ 23.82 | ≈ 25.20 | ≈ 27.23 | ≈ 26.59 | ≈ 26.36 | ≈ 26.04 | ≈ 25.58 |
| 5 | ≈ 32.20 | ≈ 31.27 | ≈ 30.68 | ≈ 33.68 | ≈ 33.20 | ≈ 32.69 | 32.17 | ≈ 32.49 | ≈ 34.43 | ≈ 37.11 | ≈ 36.09 | ≈ 35.72 | ≈ 35.19 | ≈ 34.42 |
| 6 | ≈ 41.22 | ≈ 40.38 | 39.85 | ≈ 43.89 | ≈ 43.32 | ≈ 42.65 | 41.92 | ≈ 42.05 | ≈ 44.51 | ≈ 47.95 | ≈ 46.47 | ≈ 45.96 | ≈ 45.26 | ≈ 44.22 |
| 7 | ≈ 50.46 | ≈ 49.86 | ≈ 49.52 | ≈ 54.74 | ≈ 54.21 | ≈ 53.47 | 52.57 | ≈ 52.53 | ≈ 55.53 | ≈ 59.74 | ≈ 57.65 | ≈ 56.92 | ≈ 55.89 | ≈ 54.35 |
| 8 | ≈ 59.44 | ≈ 59.28 | ≈ 59.32 | ≈ 66.01 | ≈ 65.63 | ≈ 64.92 | 63.92 | 63.74 | ≈ 67.31 | ≈ 72.40 | 69.77 | 68.80 | 67.41 | 65.27 |
| 9 | ≈ 75.67 | ≈ 76.21 | ≈ 76.81 | ≈ 77.37 | ≈ 77.16 | ≈ 76.62 | 75.69 | 75.46 | 79.68 | 85.74 | 82.62 | 81.42 | 79.67 | 76.90 |
| 10 | ≈ 84.77 | ≈ 85.93 | ≈ 87.33 | ≈ 88.51 | ≈ 88.85 | ≈ 88.57 | 87.76 | 87.54 | 92.47 | 99.60 | 96.07 | 94.65 | 92.57 | 89.25 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 96.073 | 96.067 |
| SC2 | 0 | 8 | 63.735 | 63.743 |
| SC3 | -18 | 7 | 54.535 | 54.558 |
| SC4 | -25 | 6 | 39.831 | 39.853 |
| SC5 | -34 | 6 | 41.082 | 41.089 |
| A | 2460 mm |
|---|---|
| B | 1050 mm |
| C | 1935 mm |
| F | 990 mm |
| G | 2035 mm |
| E | 2050 mm |
| G1 | 1035 mm |
| G2 | 1000 mm |
| D IN | 2 x Ø42 |
| D OUT | 2 x Ø54 |
| Length | 2460 mm |
|---|---|
| Width | 1050 mm |
| Height | 2050 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.