EK-K-s-863BG10-B08 C
163.97 kW
Defrost: None
Product code: EK-K-b-863BG10-B29 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 110,241 m³/h |
|---|---|
| External surface | 586.0 m² |
| Inner volume | 243.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 1,152 kg |
| Quantity | 8 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 15,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 77.0 dB(A) |
|---|---|
| Sound power | 101.0 dB(A) |
| Energy class | E |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø80 |
| EK-K-b-863BG10-B29 C | None |
|---|---|
| EK-K-b-863BG10-B29 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 64.33 | 62.81 | 61.90 | 61.40 | 60.74 | 60.00 | 59.23 | 60.14 | 63.59 | 68.65 | 66.93 | 66.30 | 65.41 | 64.11 |
| 5 | 77.55 | 76.49 | 75.89 | 83.95 | 83.18 | 82.13 | 80.89 | 81.65 | 86.57 | 93.45 | 90.86 | 89.99 | 88.77 | 86.96 |
| 6 | 97.62 | 97.24 | 97.21 | 107.99 | 107.41 | 106.29 | 104.75 | 105.22 | 111.39 | 120.07 | 116.23 | 114.88 | 112.99 | 110.19 |
| 7 | 116.90 | 117.77 | 118.73 | 132.93 | 132.82 | 131.85 | 130.13 | 130.39 | 137.89 | 148.60 | 143.53 | 141.64 | 138.93 | 134.73 |
| 8 | 135.34 | 137.81 | 140.11 | 157.48 | 158.26 | 157.80 | 156.34 | 156.53 | 165.50 | 178.46 | 172.24 | 169.86 | 166.34 | 160.70 |
| 9 | 169.45 | 173.52 | 177.99 | 182.04 | 183.92 | 184.18 | 183.11 | 183.39 | 193.95 | 209.32 | 202.30 | 199.45 | 195.24 | 188.36 |
| 10 | 185.63 | 192.19 | 198.32 | 203.86 | 207.16 | 208.93 | 209.28 | 210.66 | 222.90 | 240.67 | 233.01 | 229.76 | 224.92 | 216.90 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 64.15 | 62.73 | 61.85 | 61.36 | 60.69 | 59.92 | 59.03 | 60.13 | 63.58 | 68.65 | 66.93 | 66.29 | 65.41 | 64.11 |
| 5 | 77.41 | 76.40 | 75.83 | 83.88 | 83.07 | 81.86 | 80.50 | 81.62 | 86.55 | 93.43 | 90.85 | 89.98 | 88.77 | 86.95 |
| 6 | 97.47 | 97.14 | 97.14 | 107.90 | 107.25 | 105.89 | 104.15 | 105.21 | 111.31 | 120.02 | 116.14 | 114.80 | 112.94 | 110.15 |
| 7 | 116.74 | 117.66 | 118.65 | 132.82 | 132.61 | 131.32 | 129.31 | 129.95 | 137.63 | 148.34 | 142.91 | 140.98 | 138.19 | 133.89 |
| 8 | 135.17 | 137.70 | 140.03 | 157.37 | 158.02 | 157.16 | 155.33 | 155.80 | 164.72 | 177.55 | 171.04 | 168.53 | 164.82 | 158.86 |
| 9 | 169.27 | 173.40 | 177.92 | 181.92 | 183.66 | 183.44 | 181.93 | 182.39 | 192.82 | 208.02 | 200.56 | 197.51 | 192.99 | 185.59 |
| 10 | 185.45 | 192.08 | 198.25 | 203.75 | 206.70 | 208.16 | 208.07 | 209.40 | 221.46 | 238.96 | 230.76 | 227.22 | 221.97 | 213.23 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 233.011 | 230.762 |
| SC2 | 0 | 8 | 156.532 | 155.800 |
| SC3 | -18 | 7 | 133.001 | 132.865 |
| SC4 | -25 | 6 | 97.209 | 97.138 |
| SC5 | -34 | 6 | 97.667 | 97.526 |
| A | 4460 mm |
|---|---|
| B | 1150 mm |
| C | 1935 mm |
| F | 1090 mm |
| G | 4035 mm |
| E | 2050 mm |
| G1 | 1035 mm |
| G2 | 1000 mm |
| D IN | 2 x Ø54 |
| D OUT | 2 x Ø80 |
| Length | 4460 mm |
|---|---|
| Width | 1150 mm |
| Height | 2050 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.