EK-T-163BE10-B13 C
18.25 kW
Defrost: None
Product code: EK-T-163BE10-B08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 14,872 m³/h |
|---|---|
| External surface | 54.9 m² |
| Inner volume | 23.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 183 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EK-T-163BE10-B08 C | None |
|---|---|
| EK-T-163BE10-B08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.49 | 6.27 | 6.14 | 6.07 | 5.99 | 5.92 | 5.86 | 5.89 | 6.23 | 6.73 | 6.57 | 6.51 | 6.43 | 6.32 |
| 5 | 7.97 | 7.75 | 7.61 | 8.36 | 8.24 | 8.12 | 8.00 | 8.03 | 8.50 | 9.16 | 8.91 | 8.81 | 8.68 | 8.49 |
| 6 | 10.18 | 10.00 | 9.88 | 10.89 | 10.75 | 10.59 | 10.41 | 10.42 | 11.02 | 11.86 | 11.49 | 11.36 | 11.18 | 10.91 |
| 7 | 12.45 | 12.33 | 12.26 | 13.57 | 13.45 | 13.28 | 13.06 | 13.04 | 13.78 | 14.82 | 14.32 | 14.13 | 13.88 | 13.49 |
| 8 | 14.65 | 14.65 | 14.68 | 16.36 | 16.29 | 16.12 | 15.88 | 15.84 | 16.72 | 17.99 | 17.34 | 17.10 | 16.76 | 16.23 |
| 9 | 18.62 | 18.81 | 19.00 | 19.17 | 19.17 | 19.02 | 18.80 | 18.75 | 19.80 | 21.31 | 20.54 | 20.24 | 19.81 | 19.12 |
| 10 | 20.86 | 21.20 | 21.58 | 21.91 | 22.03 | 21.98 | 21.80 | 21.75 | 22.98 | 24.75 | 23.88 | 23.53 | 23.01 | 22.19 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.73 | 5.54 | 5.44 | 5.39 | 5.34 | 5.30 | 5.25 | 5.32 | 5.64 | 6.10 | 5.97 | 5.93 | 5.86 | 5.77 |
| 5 | 6.96 | 6.77 | 6.65 | 7.32 | 7.24 | 7.15 | 7.06 | 7.13 | 7.56 | 8.18 | 7.98 | 7.91 | 7.81 | 7.65 |
| 6 | 8.86 | 8.67 | 8.56 | 9.44 | 9.34 | 9.21 | 9.08 | 9.11 | 9.65 | 10.41 | 10.11 | 10.01 | 9.86 | 9.65 |
| 7 | 10.81 | 10.63 | 10.55 | 11.68 | 11.58 | 11.44 | 11.27 | 11.27 | 11.92 | 12.84 | 12.42 | 12.27 | 12.06 | 11.75 |
| 8 | 12.73 | 12.64 | 12.61 | 14.02 | 13.93 | 13.79 | 13.59 | 13.57 | 14.33 | 15.44 | 14.90 | 14.70 | 14.42 | 13.98 |
| 9 | 16.23 | 16.24 | 16.31 | 16.39 | 16.35 | 16.23 | 16.02 | 15.97 | 16.87 | 18.17 | 17.52 | 17.27 | 16.91 | 16.34 |
| 10 | 18.23 | 18.41 | 18.59 | 18.78 | 18.81 | 18.71 | 18.52 | 18.46 | 19.48 | 20.98 | 20.25 | 19.95 | 19.51 | 18.81 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 23.878 | 20.246 |
| SC2 | 0 | 8 | 15.836 | 13.567 |
| SC3 | -18 | 7 | 13.532 | 11.646 |
| SC4 | -25 | 6 | 9.875 | 8.556 |
| SC5 | -34 | 6 | 10.155 | 8.827 |
| A | 1460 mm |
|---|---|
| B | 1100 mm |
| C | 1035 mm |
| F | 840 mm |
| G | 1035 mm |
| E | 1150 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1460 mm |
|---|---|
| Width | 1100 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.