EK-T-250AE10-B10 C
19.84 kW
Defrost: None
Product code: EK-T-163BE10-B13 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,958 m³/h |
|---|---|
| External surface | 54.9 m² |
| Inner volume | 23.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 185 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.2 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EK-T-163BE10-B13 C | None |
|---|---|
| EK-T-163BE10-B13 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.00 | 6.76 | 6.61 | 6.53 | 6.44 | 6.35 | 6.27 | 6.28 | 6.64 | 7.17 | 6.99 | 6.92 | 6.83 | 6.70 |
| 5 | 8.63 | 8.40 | 8.25 | 9.06 | 8.93 | 8.79 | 8.65 | 8.65 | 9.14 | 9.84 | 9.54 | 9.44 | 9.29 | 9.07 |
| 6 | 11.07 | 10.86 | 10.75 | 11.85 | 11.71 | 11.54 | 11.34 | 11.31 | 11.94 | 12.85 | 12.43 | 12.28 | 12.08 | 11.77 |
| 7 | 13.48 | 13.40 | 13.37 | 14.83 | 14.70 | 14.53 | 14.30 | 14.23 | 15.03 | 16.16 | 15.59 | 15.39 | 15.10 | 14.66 |
| 8 | 15.83 | 15.91 | 16.00 | 17.87 | 17.83 | 17.68 | 17.45 | 17.36 | 18.33 | 19.71 | 19.01 | 18.75 | 18.37 | 17.78 |
| 9 | 20.07 | 20.39 | 20.62 | 20.88 | 20.95 | 20.87 | 20.69 | 20.61 | 21.77 | 23.44 | 22.61 | 22.30 | 21.84 | 21.10 |
| 10 | 22.22 | 22.75 | 23.27 | 23.77 | 24.06 | 24.12 | 24.00 | 23.95 | 25.31 | 27.29 | 26.38 | 26.02 | 25.49 | 24.62 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.10 | 5.91 | 5.80 | 5.74 | 5.68 | 5.62 | 5.57 | 5.63 | 5.96 | 6.45 | 6.31 | 6.25 | 6.18 | 6.08 |
| 5 | 7.44 | 7.24 | 7.12 | 7.83 | 7.74 | 7.64 | 7.53 | 7.60 | 8.06 | 8.70 | 8.48 | 8.40 | 8.28 | 8.11 |
| 6 | 9.48 | 9.30 | 9.18 | 10.13 | 10.02 | 9.88 | 9.73 | 9.76 | 10.33 | 11.14 | 10.81 | 10.69 | 10.53 | 10.30 |
| 7 | 11.57 | 11.43 | 11.34 | 12.56 | 12.46 | 12.31 | 12.11 | 12.12 | 12.81 | 13.79 | 13.33 | 13.17 | 12.94 | 12.59 |
| 8 | 13.61 | 13.56 | 13.56 | 15.10 | 15.02 | 14.86 | 14.65 | 14.62 | 15.45 | 16.63 | 16.04 | 15.82 | 15.51 | 15.03 |
| 9 | 17.32 | 17.41 | 17.53 | 17.66 | 17.64 | 17.51 | 17.30 | 17.25 | 18.22 | 19.62 | 18.91 | 18.64 | 18.24 | 17.61 |
| 10 | 19.43 | 19.70 | 19.97 | 20.18 | 20.25 | 20.18 | 19.99 | 19.94 | 21.06 | 22.69 | 21.89 | 21.56 | 21.09 | 20.33 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 26.381 | 21.886 |
| SC2 | 0 | 8 | 17.363 | 14.623 |
| SC3 | -18 | 7 | 14.793 | 12.529 |
| SC4 | -25 | 6 | 10.747 | 9.183 |
| SC5 | -34 | 6 | 11.044 | 9.452 |
| A | 1460 mm |
|---|---|
| B | 1158 mm |
| C | 1035 mm |
| F | 840 mm |
| G | 1035 mm |
| E | 1150 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 1460 mm |
|---|---|
| Width | 1158 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.