Skip to Content

Blast freezer EK-T-463BG10-B13 C

Blast freezer EK-T-463BG10-B13 C
Illustrative photo

Producer: Karyer · Line: EK-T (Blast Freezers)

Product code: EK-T-463BG10-B13 C

Cooling capacity i
90.66 kW
Air flow
63,979 m³/h
Fin spacing
10.0 mm
Fans
4 × ⌀630 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EK-T — EK-T - blast freezer
  • B
    Number of fans: 4 — Number of fans (one digit).
  • C
    Fan diameter: 63 — Ø630 mm
  • D
    Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: G — 8 tube rows
  • F
    Fin spacing: 10 — Fin spacing about 10 mm
  • G
    Generation code: B — Generation B
  • H
    Fan data: 13 — Ø630: 400V/3Ph/50Hz, 4-pole

Data

Evaporator
Air flow 63,979 m³/h
External surface 293.0 m²
Inner volume 120.0 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 639 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,330 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 70.0 dB(A)
Sound power 93.2 dB(A)
Energy class E
Connections
Inlet Ø42
Outlet Ø54
Defrost
EK-T-463BG10-B13 C None
EK-T-463BG10-B13 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
86.502 kW
Low speed (Y)
70.705 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 34.88 34.09 33.60 33.29 32.90 32.46 32.01 32.25 34.07 36.74 35.74 35.38 34.87 34.11
5 42.28 41.68 41.42 45.84 45.42 44.83 44.13 44.36 46.96 50.61 49.12 48.60 47.88 46.67
6 53.02 53.06 53.19 59.27 58.94 58.36 57.52 57.67 61.00 65.70 63.57 62.80 61.72 60.10
7 63.36 64.20 64.99 72.97 73.06 72.64 71.80 71.78 75.90 81.78 79.01 77.97 76.47 74.14
8 73.14 74.67 76.33 86.38 87.06 87.02 86.38 86.50 91.48 98.66 95.32 94.01 92.11 89.06
9 90.46 93.45 96.26 98.82 100.40 101.20 101.25 101.53 107.43 116.03 112.27 110.76 108.51 104.84
10 99.16 103.32 107.13 110.53 112.70 113.87 114.29 115.16 122.12 132.31 128.93 127.50 125.24 121.00

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 29.62 28.90 28.50 28.31 28.05 27.75 27.46 27.97 29.62 32.01 31.26 30.99 30.61 30.04
5 35.55 34.99 34.68 38.37 38.05 37.63 37.16 37.50 39.78 42.99 41.85 41.47 40.94 40.18
6 44.68 44.35 44.17 49.10 48.82 48.36 47.77 47.92 50.74 54.74 53.04 52.44 51.59 50.34
7 53.56 53.67 53.92 60.24 60.12 59.67 59.03 59.04 62.43 67.31 65.13 64.31 63.14 61.30
8 62.11 62.85 63.61 71.48 71.64 71.37 70.77 70.71 74.76 80.63 77.92 76.89 75.37 72.92
9 78.07 79.74 81.06 82.46 83.06 83.07 82.63 82.63 87.39 94.29 91.22 89.98 88.15 85.18
10 86.09 88.64 91.05 93.27 94.47 94.85 94.62 94.79 100.29 108.26 104.91 103.48 101.38 97.87

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 128.930104.907
SC2 0 8 86.50270.705
SC3 -18 7 73.08060.241
SC4 -25 6 53.19244.167
SC5 -34 6 53.10144.663

Dimensions

Dimension drawing of EK-T-463BG10-B13 C
Dimension drawing
Dimensions as drawn
A 4460 mm
B 1258 mm
C 1035 mm
F 940 mm
G 4035 mm
E 1150 mm
G1 1035 mm
G2 1000 mm
D IN 2 x Ø42
D OUT 2 x Ø54
Overall [mm]
Length 4460 mm
Width 1258 mm
Height 1150 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.