EA-DA-x-150BE7-B21 C
8.88 kW
Defrost: None
Product code: EA-DA-145AE7-C23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,485 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 38.0 m² |
| Inner volume | 11.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 76 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,300 rpm |
| Power | 350 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-DA-145AE7-C23 C | None |
|---|---|
| EA-DA-145AE7-C23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.24 | 3.24 | 3.26 | 3.28 | 3.29 | 3.28 | 3.26 | 3.32 | 3.53 | 3.83 | 3.75 | 3.72 | 3.68 | 3.61 |
| 5 | 4.20 | 4.25 | 4.29 | 4.35 | 4.37 | 4.37 | 4.35 | 4.39 | 4.66 | 5.05 | 4.93 | 4.89 | 4.83 | 4.74 |
| 6 | 5.11 | 5.23 | 5.35 | 5.46 | 5.51 | 5.52 | 5.50 | 5.54 | 5.88 | 6.36 | 6.19 | 6.13 | 6.03 | 5.89 |
| 7 | 5.96 | 6.18 | 6.39 | 6.53 | 6.64 | 6.68 | 6.68 | 6.73 | 7.13 | 7.73 | 7.51 | 7.43 | 7.31 | 7.10 |
| 8 | 6.75 | 7.04 | 7.34 | 7.61 | 7.77 | 7.86 | 7.89 | 7.95 | 8.43 | 9.13 | 8.89 | 8.79 | 8.63 | 8.38 |
| 9 | 7.41 | 7.83 | 8.22 | 8.56 | 8.80 | 8.95 | 9.03 | 9.14 | 9.71 | 10.54 | 10.29 | 10.17 | 9.99 | 9.68 |
| 10 | 8.03 | 8.57 | 9.06 | 9.50 | 9.80 | 10.00 | 10.12 | 10.25 | 10.89 | 11.82 | 11.57 | 11.45 | 11.26 | 10.95 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.565 |
| SC2 | 0 | 8 | 7.949 |
| SC3 | -18 | 7 | 6.581 |
| SC4 | -25 | 6 | 5.351 |
| SC5 | -34 | 6 | 5.139 |
| A | 1217 mm |
|---|---|
| B | 875 mm |
| C | 710 mm |
| F | 710 mm |
| E | 785 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1217 mm |
|---|---|
| Width | 875 mm |
| Height | 710 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.