Skip to Content

Unit cooler EA-DA-x-150BE7-B21 C

Unit cooler EA-DA-x-150BE7-B21 C
Illustrative photo

Producer: Karyer · Line: EA-DA (Fruit and Vegetable)

Product code: EA-DA-x-150BE7-B21 C

Cooling capacity i
8.88 kW
Air flow
7,230 m³/h
Fin spacing
7.0 mm
Air throw
21 m
Fans
1 × ⌀500 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA-DA — EA-DA - fruit and vegetable unit cooler (blowing fans)
  • C
    Number of fans: 1 — Number of fans (one digit).
  • D
    Fan diameter: 50 — Ø500 mm
  • E
    Dimensional data - coil size letter: B — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • F
    Dimensional data - tube rows: E — 6 tube rows
  • G
    Fin spacing: 7 — Fin spacing about 7 mm
  • H
    Generation code: B — Generation B
  • I
    Fan data: 21 — Ø350: 230V/1Ph/50Hz, 4-pole; Ø500: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 7,230 m³/h
Air throw 21 m
External surface 59.2 m²
Inner volume 17.0 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 101 kg
Fans
Quantity 1
Diameter 500 mm
Speed 1,300 rpm
Power 680 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 57.0 dB(A)
Sound power 78.9 dB(A)
Energy class D
Connections
Inlet Ø12,7
Outlet Ø19
Defrost
EA-DA-x-150BE7-B21 C None
EA-DA-x-150BE7-B21 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
8.589 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 not rated 3.06 3.31 3.52 3.67 3.77 3.82 3.89 4.15 4.52 4.44 4.41 4.36 4.29
5 not rated not rated 4.17 4.45 4.72 4.91 5.04 5.19 5.54 6.05 5.97 5.94 5.88 5.79
6 ≈ 2.05 ≈ 4.15 4.85 5.31 5.68 5.97 6.19 6.39 6.84 7.49 7.43 7.40 7.35 7.25
7 ≈ 1.65 ≈ 3.51 ≈ 5.47 6.05 6.54 6.94 7.24 7.50 8.04 8.83 8.77 8.74 8.68 8.56
8 1.85 ≈ 1.83 ≈ 6.02 6.74 7.35 7.86 8.25 8.59 9.22 10.14 10.11 10.08 10.02 9.89
9 2.05 ≈ 2.02 ≈ 4.48 ≈ 7.36 8.11 8.73 9.23 9.65 10.37 11.44 11.44 11.41 11.36 11.22
10 2.25 2.21 ≈ 2.23 ≈ 7.93 8.80 9.55 10.17 10.68 11.50 12.71 12.75 12.73 12.68 12.55

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 12.746
SC2 0 8 8.589
SC3 -18 7 6.260
SC4 -25 6 4.848
SC5 -34 6 2.587

Dimensions

Dimension drawing of EA-DA-x-150BE7-B21 C
Dimension drawing
Dimensions as drawn
A 1487 mm
B 950 mm
C 810 mm
F 710 mm
E 1035 mm
D IN 1 x Ø12,7
D OUT 1 x Ø19
Overall [mm]
Length 1487 mm
Width 950 mm
Height 810 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.