EA-DA-x-235BE7-B21 C
6.12 kW
Defrost: None
Product code: SP.-EA-DA-x-145AE7-B23 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
| Air flow | 4,491 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 38.0 m² |
| Inner volume | 11.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 74 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,300 rpm |
| Power | 350 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø15,9 |
| SP.-EA-DA-x-145AE7-B23 C | None |
|---|---|
| SP.-EA-DA-x-145AE7-B23 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | 2.01 | 2.20 | 2.33 | 2.44 | 2.55 | 2.74 | 3.02 | 3.01 | 3.01 | 3.00 | 2.97 |
| 5 | not rated | not rated | not rated | not rated | 2.72 | 2.93 | 3.09 | 3.24 | 3.49 | 3.85 | 3.86 | 3.86 | 3.86 | 3.84 |
| 6 | not rated | not rated | 1.22 | ≈ 2.86 | 3.17 | 3.44 | 3.67 | 3.87 | 4.17 | 4.62 | 4.65 | 4.66 | 4.65 | 4.63 |
| 7 | 1.06 | 1.05 | ≈ 1.05 | ≈ 1.94 | ≈ 3.58 | 3.92 | 4.22 | 4.48 | 4.84 | 5.38 | 5.43 | 5.44 | 5.45 | 5.43 |
| 8 | 1.19 | 1.18 | 1.18 | ≈ 1.20 | ≈ 3.95 | 4.37 | 4.73 | 5.05 | 5.47 | 6.10 | 6.19 | 6.21 | 6.23 | 6.21 |
| 9 | 1.32 | 1.30 | 1.30 | ≈ 1.32 | ≈ 2.41 | ≈ 4.77 | 5.21 | 5.60 | 6.08 | 6.80 | 6.93 | 6.96 | 6.99 | 6.99 |
| 10 | 1.44 | 1.42 | 1.43 | 1.45 | ≈ 1.47 | ≈ 5.15 | 5.66 | 6.12 | 6.66 | 7.47 | 7.65 | 7.69 | 7.74 | 7.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.649 |
| SC2 | 0 | 8 | 5.052 |
| SC3 | -18 | 7 | 3.196 |
| SC4 | -25 | 6 | 1.221 |
| SC5 | -34 | 6 | — |
| A | 1217 mm |
|---|---|
| B | 875 mm |
| C | 710 mm |
| F | 710 mm |
| E | 785 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø15,9 |
| Length | 1157 mm |
|---|---|
| Width | 875 mm |
| Height | 710 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.