EA-DI-191GG10-A04 C
39.09 kW
Defrost: None
Product code: EA-DI-163GI4-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,675 m³/h |
|---|---|
| External surface | 271.2 m² |
| Inner volume | 54.0 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 310 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-DI-163GI4-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 16.12 | 16.23 | 16.41 | 16.63 | 16.73 | 16.74 | 16.68 | 17.04 | 18.16 | 19.75 | 19.38 | 19.25 | 19.08 | 18.84 |
| 5 | 20.42 | 20.76 | 21.12 | 21.44 | 21.62 | 21.66 | 21.57 | 21.88 | 23.25 | 25.24 | 24.61 | 24.38 | 24.04 | 23.52 |
| 6 | 24.46 | 25.13 | 25.77 | 26.35 | 26.67 | 26.76 | 26.65 | 26.92 | 28.56 | 30.93 | 30.07 | 29.73 | 29.22 | 28.39 |
| 7 | 28.23 | 29.33 | 30.20 | 31.07 | 31.60 | 31.83 | 31.80 | 32.05 | 33.97 | 36.79 | 35.72 | 35.28 | 34.62 | 33.51 |
| 8 | 31.74 | 33.12 | 34.52 | 35.76 | 36.56 | 36.95 | 36.99 | 37.28 | 39.51 | 42.75 | 41.54 | 41.00 | 40.18 | 38.77 |
| 9 | 34.69 | 36.67 | 38.49 | 40.09 | 41.17 | 41.78 | 42.02 | 42.43 | 45.00 | 48.75 | 47.41 | 46.79 | 45.83 | 44.12 |
| 10 | 37.52 | 40.01 | 42.30 | 44.30 | 45.69 | 46.50 | 46.87 | 47.35 | 50.22 | 54.38 | 53.01 | 52.36 | 51.36 | 49.51 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.39 | 13.40 | 13.49 | 13.64 | 13.71 | 13.72 | 13.67 | 13.98 | 14.90 | 16.21 | 15.90 | 15.79 | 15.64 | 15.43 |
| 5 | 16.88 | 17.01 | 17.21 | 17.45 | 17.56 | 17.58 | 17.49 | 17.75 | 18.86 | 20.48 | 19.97 | 19.78 | 19.50 | 19.05 |
| 6 | 20.35 | 20.65 | 20.99 | 21.31 | 21.50 | 21.54 | 21.44 | 21.65 | 22.97 | 24.90 | 24.20 | 23.92 | 23.50 | 22.81 |
| 7 | 23.61 | 24.16 | 24.70 | 25.22 | 25.50 | 25.58 | 25.47 | 25.65 | 27.18 | 29.42 | 28.55 | 28.19 | 27.63 | not rated |
| 8 | 26.68 | 27.54 | 28.35 | 29.07 | 29.49 | 29.59 | 29.52 | 29.70 | 31.45 | 33.98 | 32.99 | 32.54 | 31.87 | not rated |
| 9 | 29.56 | 30.78 | 31.76 | 32.75 | 33.35 | 33.64 | 33.61 | 33.80 | 35.78 | 38.65 | 37.52 | 37.00 | not rated | not rated |
| 10 | 32.24 | 33.68 | 35.11 | 36.39 | 37.23 | 37.64 | 37.70 | 37.92 | 40.14 | 43.36 | 42.10 | 41.50 | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 53.014 | 42.098 |
| SC2 | 0 | 8 | 37.281 | 29.698 |
| SC3 | -18 | 7 | 31.322 | 25.362 |
| SC4 | -25 | 6 | 25.771 | 20.993 |
| SC5 | -34 | 6 | 24.629 | 20.439 |
| A | 1725 mm |
|---|---|
| B | 1200 mm |
| C | 1150 mm |
| F | 1160 mm |
| G | 1740 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1740 mm |
| Height | 1150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.