Skip to Content

Unit cooler EA-DI-191GG10-A04 C

Unit cooler EA-DI-191GG10-A04 C
Illustrative photo

Producer: Karyer · Line: EA-DI (Cold Store)

Product code: EA-DI-191GG10-A04 C

Cooling capacity i
39.09 kW
Air flow
24,248 m³/h
Fin spacing
10.0 mm
Fans
1 × ⌀910 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA-DI — EA-DI - cold-store evaporator, fans inclined 45° to the coil
  • B
    Number of fans: 1 — Number of fans (one digit).
  • C
    Fan diameter: 91 — Ø910 mm
  • D
    Dimensional data - coil size letter: G — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: G — 8 tube rows
  • F
    Fin spacing: 10 — Fin spacing about 10 mm
  • G
    Generation code: A — Generation A
  • H
    Fan data: 04 — Ø910: 400V/3Ph/50Hz, 6-pole

Data

Evaporator
Air flow 24,248 m³/h
External surface 127.0 m²
Inner volume 53.6 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 339 kg
Fans
Quantity 1
Diameter 910 mm
Speed 840 rpm
Power 2,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 68.0 dB(A)
Sound power 91.0 dB(A)
Energy class D
Connections
Inlet Ø35
Outlet Ø54
Defrost
EA-DI-191GG10-A04 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
37.361 kW
Low speed (Y)
29.513 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 15.31 15.04 14.88 14.80 14.66 14.48 14.28 14.58 15.42 16.65 16.22 16.07 15.85 15.53
5 20.33 20.21 20.16 20.15 20.01 19.78 19.48 19.73 20.93 22.61 21.98 21.77 21.47 21.04
6 25.40 25.52 25.68 25.82 25.73 25.50 25.14 25.34 26.84 28.95 28.01 27.68 27.22 26.52
7 30.20 30.71 31.18 31.58 31.67 31.51 31.13 31.26 33.08 35.65 34.42 33.96 33.28 32.24
8 34.73 35.71 36.45 37.20 37.53 37.52 37.22 37.36 39.52 42.66 41.16 40.59 39.73 38.35
9 38.68 40.09 41.41 42.58 43.30 43.62 43.43 43.61 46.14 49.83 48.18 47.50 46.48 44.81
10 42.32 44.24 46.00 47.55 48.49 49.00 49.12 49.55 52.53 56.88 55.30 54.52 53.36 51.41

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 12.65 12.40 12.27 12.23 12.14 12.02 11.87 12.24 13.07 14.15 13.86 13.75 13.59 13.35
5 16.71 16.51 16.42 16.39 16.28 16.10 15.86 16.17 17.19 18.61 18.13 17.98 17.77 17.49
6 20.86 20.71 20.73 20.78 20.69 20.48 20.15 20.40 21.63 23.36 22.62 22.35 21.98 21.43
7 24.88 24.99 25.16 25.33 25.28 25.07 24.69 24.87 26.31 28.40 27.39 26.99 26.45 not rated
8 28.76 29.15 29.54 29.91 29.98 29.81 29.39 29.51 31.20 33.67 not rated not rated not rated not rated
9 32.46 33.19 33.88 34.47 34.63 34.52 34.13 34.27 36.21 38.98 not rated not rated not rated not rated
10 35.95 36.96 37.98 38.86 39.25 39.29 38.94 39.11 41.29 44.51 not rated not rated not rated not rated

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 55.295—
SC2 0 8 37.36129.513
SC3 -18 7 31.65025.315
SC4 -25 6 25.67820.731
SC5 -34 6 25.46520.862

Dimensions

Dimension drawing of EA-DI-191GG10-A04 C
Dimension drawing
Dimensions as drawn
A 1725 mm
B 1100 mm
C 1350 mm
F 1060 mm
G 1900 mm
E 1335 mm
D IN 1 x Ø35
D OUT 1 x Ø54
Overall [mm]
Length 1725 mm
Width 1900 mm
Height 1350 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.