EA-DI-491GG7-A04 C
160.68 kW
Defrost: None
Product code: EA-DI-491GE4-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 93,583 m³/h |
|---|---|
| External surface | 781.9 m² |
| Inner volume | 157.9 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 1,184 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 97.3 dB(A) |
| Energy class | E |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø80 |
| EA-DI-491GE4-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 60.20 | 61.91 | 63.38 | 64.60 | 65.12 | 65.13 | 64.72 | 66.57 | 70.96 | 76.76 | 75.15 | 74.54 | 73.67 | 72.36 |
| 5 | 76.32 | 79.49 | 82.72 | 85.41 | 86.93 | 87.51 | 87.32 | 89.16 | 94.91 | 103.01 | 100.64 | 99.84 | 98.74 | 97.06 |
| 6 | 89.55 | 94.97 | 99.89 | 104.18 | 107.06 | 108.77 | 109.53 | 111.73 | 118.96 | 129.39 | 126.80 | 125.81 | 124.34 | 121.66 |
| 7 | 101.43 | 108.92 | 115.79 | 121.80 | 125.98 | 128.59 | 129.88 | 132.33 | 140.82 | 153.18 | 149.95 | 148.65 | 146.68 | 143.44 |
| 8 | ≈ 112.12 | 121.85 | 130.88 | 138.83 | 144.54 | 148.29 | 150.30 | 153.14 | 162.96 | 177.35 | 173.55 | 171.96 | 169.52 | 165.39 |
| 9 | ≈ 121.68 | 133.73 | 145.04 | 155.15 | 162.64 | 167.72 | 170.67 | 174.03 | 185.24 | 201.71 | 197.50 | 195.64 | 192.76 | 187.77 |
| 10 | ≈ 116.31 | ≈ 144.54 | 158.26 | 170.69 | 180.14 | 186.65 | 190.74 | 194.91 | 207.55 | 226.08 | 221.68 | 219.57 | 216.29 | 210.49 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 54.51 | 58.29 | 63.42 | 62.44 | 62.21 | 61.57 | 60.66 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 71.44 | 76.04 | 82.65 | 80.68 | 80.03 | 79.15 | 77.91 |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 221.675 | — |
| SC2 | 0 | 8 | 153.139 | — |
| SC3 | -18 | 7 | 123.671 | — |
| SC4 | -25 | 6 | 99.892 | — |
| SC5 | -34 | 6 | 90.807 | — |
| A | 5625 mm |
|---|---|
| B | 1000 mm |
| C | 1350 mm |
| F | 960 mm |
| G | 1800 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 5235 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø80 |
| Length | 5625 mm |
|---|---|
| Width | 1800 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.