EA-DI-491GE4-A04 C
158.91 kW
Defrost: None
Product code: EA-DI-491GG7-A04 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 91,865 m³/h |
|---|---|
| External surface | 703.0 m² |
| Inner volume | 204.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 1,254 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 97.5 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø66,7 |
| EA-DI-491GG7-A04 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 61.82 | 62.21 | 62.68 | 63.15 | 63.16 | 62.84 | 62.27 | 63.88 | 67.97 | 73.54 | 71.89 | 71.27 | 70.39 | 69.06 |
| 5 | 80.29 | 81.97 | 83.47 | 84.75 | 85.17 | 84.85 | 84.13 | 85.61 | 91.00 | 98.56 | 96.08 | 95.26 | 94.12 | 92.38 |
| 6 | 97.40 | 100.97 | 103.56 | 106.17 | 107.51 | 107.81 | 107.24 | 108.66 | 115.33 | 124.83 | 121.23 | 119.92 | 118.02 | 115.08 |
| 7 | 112.42 | 117.72 | 122.58 | 126.88 | 129.64 | 131.17 | 131.10 | 132.64 | 140.73 | 152.43 | 148.01 | 146.27 | 143.68 | 139.49 |
| 8 | 125.71 | 133.03 | 139.71 | 145.55 | 149.46 | 151.74 | 152.65 | 154.78 | 164.43 | 178.62 | 174.24 | 172.46 | 169.76 | 165.00 |
| 9 | 137.88 | 147.40 | 156.11 | 163.74 | 169.01 | 172.24 | 173.68 | 176.16 | 187.14 | 203.25 | 198.37 | 196.26 | 193.05 | 187.46 |
| 10 | ≈ 148.96 | 160.83 | 171.76 | 181.36 | 188.04 | 192.40 | 194.62 | 197.62 | 209.97 | 228.03 | 222.76 | 220.35 | 216.64 | 210.04 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 52.35 | 55.98 | 60.86 | 59.87 | 59.52 | 58.91 | 57.99 |
| 5 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | 74.48 |
| 6 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 7 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 8 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 9 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| 10 | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated | not rated |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 222.756 | — |
| SC2 | 0 | 8 | 154.783 | — |
| SC3 | -18 | 7 | 128.151 | — |
| SC4 | -25 | 6 | 103.556 | — |
| SC5 | -34 | 6 | 98.310 | — |
| A | 5625 mm |
|---|---|
| B | 1100 mm |
| C | 1350 mm |
| F | 1060 mm |
| G | 1900 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 5235 mm |
| D IN | 2 x Ø35 |
| D OUT | 2 x Ø66,7 |
| Length | 5625 mm |
|---|---|
| Width | 1900 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.