Skip to Content

Unit cooler EA-DR-350EB10-A10 C

Unit cooler EA-DR-350EB10-A10 C
Illustrative photo

Producer: Karyer · Line: EA-DR (Banana Ripnening)

Product code: EA-DR-350EB10-A10 C

Cooling capacity i
17.41 kW
Air flow
24,766 m³/h
Fin spacing
10.0 mm
Air throw
25 m
Fans
3 × ⌀500 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA-DR — EA-DR - banana ripening unit cooler
  • B
    Number of fans: 3 — Number of fans (one digit).
  • C
    Fan diameter: 50 — Ø500 mm
  • D
    Dimensional data - coil size letter: E — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: B — 3 tube rows
  • F
    Fin spacing: 10 — Fin spacing about 10 mm
  • G
    Generation code: A — Generation A
  • H
    Fan data: 10 — Ø500: 400V/3Ph/50Hz, 4-pole

Data

Evaporator
Air flow 24,766 m³/h
Air throw 25 m
External surface 63.5 m²
Inner volume 25.6 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 180 kg
Fans
Quantity 3
Diameter 500 mm
Speed 1,360 rpm
Power 2,070 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 63.0 dB(A)
Sound power 86.0 dB(A)
Energy class E
Connections
Inlet Ø19
Outlet Ø28
Defrost
EA-DR-350EB10-A10 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
16.790 kW
Low speed (Y)
15.308 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 not rated not rated 6.73 6.94 7.06 7.10 7.12 7.16 7.59 8.20 7.99 7.91 7.78 7.60
5 7.72 8.25 8.65 9.06 9.34 9.52 9.63 9.73 10.34 11.21 10.97 10.88 10.73 10.50
6 8.89 9.73 10.41 11.02 11.47 11.81 12.04 12.25 13.06 14.23 14.02 13.93 13.79 13.53
7 ≈ 10.09 11.05 11.96 12.78 13.42 13.89 14.24 14.53 15.49 16.91 16.69 16.59 16.44 16.17
8 ≈ 8.96 ≈ 12.25 13.40 14.46 15.29 15.93 16.40 16.79 17.92 19.59 19.37 19.27 19.11 18.82
9 ≈ 5.88 ≈ 13.34 14.74 16.04 17.09 17.91 18.53 19.03 20.34 22.26 22.06 21.96 21.79 21.48
10 ≈ 4.47 ≈ 14.32 15.97 17.52 18.80 19.82 20.61 21.24 22.72 24.91 24.74 24.64 24.48 24.15

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 not rated not rated 6.16 6.32 6.39 6.43 6.44 6.48 6.87 7.43 7.24 7.17 7.07 6.91
5 7.22 7.64 8.01 8.27 8.49 8.61 8.68 8.77 9.31 10.09 9.86 9.77 9.64 9.44
6 8.53 9.09 9.67 10.18 10.55 10.81 10.97 11.12 11.82 12.85 12.60 12.50 12.35 12.09
7 ≈ 9.58 10.39 11.15 11.84 12.35 12.74 13.01 13.25 14.11 15.39 15.17 15.07 14.93 14.67
8 ≈ 10.53 11.56 12.54 13.42 14.11 14.62 15.00 15.31 16.33 17.82 17.60 17.49 17.33 17.04
9 ≈ 8.90 ≈ 12.63 13.83 14.93 15.80 16.47 16.96 17.36 18.53 20.26 20.03 19.92 19.74 19.42
10 ≈ 5.68 ≈ 13.60 15.03 16.35 17.42 18.26 18.88 19.39 20.72 22.67 22.46 22.35 22.16 21.82

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 24.73922.459
SC2 0 8 16.79015.308
SC3 -18 7 13.05712.062
SC4 -25 6 10.4059.671
SC5 -34 6 9.1528.673

Dimensions

Dimension drawing of EA-DR-350EB10-A10 C
Dimension drawing
Dimensions as drawn
A 2987 mm
B 740 mm
C 875 mm
F 660 mm
E1 884 mm
E2 867 mm
E 2635 mm
D IN 1 x Ø19
D OUT 1 x Ø28
Overall [mm]
Length 2987 mm
Width 740 mm
Height 875 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.