EA-DV-191GE10-A04 C
32.21 kW
Defrost: None
Product code: EA-DV-163GI10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,098 m³/h |
|---|---|
| External surface | 132.0 m² |
| Inner volume | 54.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 318 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 69.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-DV-163GI10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.23 | 13.09 | 13.05 | 13.06 | 13.01 | 12.93 | 12.82 | 12.96 | 13.76 | 14.90 | 14.56 | 14.45 | 14.29 | 14.01 |
| 5 | 17.18 | 17.18 | 17.25 | 17.36 | 17.35 | 17.27 | 17.13 | 17.23 | 18.26 | 19.74 | 19.21 | 19.01 | 18.74 | 18.33 |
| 6 | 21.12 | 21.33 | 21.57 | 21.81 | 21.87 | 21.83 | 21.69 | 21.76 | 23.04 | 24.90 | 24.17 | 23.89 | 23.49 | 22.87 |
| 7 | 24.82 | 25.33 | 25.82 | 26.28 | 26.50 | 26.53 | 26.40 | 26.47 | 28.02 | 30.28 | 29.37 | 29.01 | 28.45 | 27.56 |
| 8 | 28.29 | 29.17 | 29.99 | 30.60 | 31.02 | 31.19 | 31.14 | 31.25 | 33.09 | 35.77 | 34.69 | 34.25 | 33.58 | 32.47 |
| 9 | 31.54 | 32.70 | 33.87 | 34.91 | 35.53 | 35.86 | 35.93 | 36.10 | 38.24 | 41.35 | 40.16 | 39.65 | 38.86 | 37.53 |
| 10 | 34.31 | 35.97 | 37.50 | 38.87 | 39.77 | 40.35 | 40.63 | 40.97 | 43.42 | 46.97 | 45.68 | 45.10 | 44.21 | 42.69 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.25 | 11.10 | 11.05 | 11.06 | 11.03 | 10.97 | 10.88 | 11.06 | 11.76 | 12.75 | 12.49 | 12.40 | 12.28 | 12.10 |
| 5 | 14.58 | 14.49 | 14.50 | 14.56 | 14.55 | 14.47 | 14.34 | 14.48 | 15.36 | 16.63 | 16.19 | 16.04 | 15.82 | 15.49 |
| 6 | 17.87 | 17.91 | 18.03 | 18.18 | 18.21 | 18.14 | 17.99 | 18.09 | 19.17 | 20.73 | 20.12 | 19.89 | 19.55 | 19.02 |
| 7 | 21.14 | 21.35 | 21.60 | 21.87 | 21.95 | 21.92 | 21.77 | 21.84 | 23.12 | 25.00 | 24.22 | 23.91 | 23.46 | 22.73 |
| 8 | 24.21 | 24.66 | 25.11 | 25.54 | 25.75 | 25.76 | 25.62 | 25.69 | 27.19 | 29.37 | 28.46 | 28.08 | 27.52 | 26.58 |
| 9 | 27.13 | 27.86 | 28.55 | 29.18 | 29.51 | 29.57 | 29.49 | 29.58 | 31.31 | 33.79 | 32.78 | 32.34 | 31.68 | 30.57 |
| 10 | 29.86 | 30.93 | 31.80 | 32.67 | 33.17 | 33.40 | 33.38 | 33.52 | 35.48 | 38.31 | 37.19 | 36.69 | 35.93 | 34.64 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 45.678 | 37.193 |
| SC2 | 0 | 8 | 31.248 | 25.693 |
| SC3 | -18 | 7 | 26.389 | 21.900 |
| SC4 | -25 | 6 | 21.569 | 18.026 |
| SC5 | -34 | 6 | 21.191 | 17.897 |
| A | 1725 mm |
|---|---|
| B | 1200 mm |
| C | 1260 mm |
| F | 1160 mm |
| G | 1885 mm |
| E | 1335 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 1725 mm |
|---|---|
| Width | 1885 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.