EA-DV-191GE10-A04 C
32.21 kW
Defrost: None
Product code: EA-DV-263GC10-A08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 34,345 m³/h |
|---|---|
| External surface | 105.5 m² |
| Inner volume | 43.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 421 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| EA-DV-263GC10-A08 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.24 | 11.94 | 11.76 | 11.65 | 11.53 | 11.39 | 11.27 | 11.23 | 11.87 | 12.80 | 12.46 | 12.33 | 12.15 | 11.89 |
| 5 | 16.45 | 16.24 | 16.12 | 16.05 | 15.92 | 15.74 | 15.55 | 15.49 | 16.37 | 17.63 | 17.11 | 16.92 | 16.64 | 16.22 |
| 6 | 20.75 | 20.71 | 20.73 | 20.78 | 20.68 | 20.52 | 20.31 | 20.21 | 21.35 | 23.00 | 22.28 | 22.02 | 21.64 | 21.06 |
| 7 | 24.85 | 25.11 | 25.37 | 25.62 | 25.67 | 25.58 | 25.39 | 25.29 | 26.73 | 28.80 | 27.89 | 27.55 | 27.06 | 26.30 |
| 8 | 28.76 | 29.27 | 29.86 | 30.38 | 30.64 | 30.69 | 30.60 | 30.55 | 32.32 | 34.87 | 33.83 | 33.42 | 32.83 | 31.89 |
| 9 | 32.12 | 33.09 | 34.02 | 34.90 | 35.48 | 35.85 | 35.92 | 35.96 | 38.07 | 41.14 | 40.00 | 39.54 | 38.87 | 37.77 |
| 10 | 35.26 | 36.63 | 37.90 | 39.07 | 39.85 | 40.37 | 40.67 | 40.95 | 43.46 | 47.15 | 46.14 | 45.73 | 45.04 | 43.80 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.94 | 10.66 | 10.50 | 10.42 | 10.33 | 10.24 | 10.15 | 10.14 | 10.72 | 11.58 | 11.29 | 11.18 | 11.04 | 10.82 |
| 5 | 14.64 | 14.39 | 14.26 | 14.20 | 14.09 | 13.96 | 13.81 | 13.77 | 14.56 | 15.71 | 15.28 | 15.12 | 14.90 | 14.55 |
| 6 | 18.45 | 18.30 | 18.22 | 18.24 | 18.17 | 18.04 | 17.85 | 17.79 | 18.81 | 20.27 | 19.68 | 19.46 | 19.14 | 18.66 |
| 7 | 22.14 | 22.19 | 22.30 | 22.44 | 22.45 | 22.34 | 22.16 | 22.10 | 23.37 | 25.19 | 24.44 | 24.16 | 23.75 | 23.08 |
| 8 | 25.71 | 26.02 | 26.35 | 26.68 | 26.82 | 26.80 | 26.63 | 26.60 | 28.12 | 30.34 | 29.43 | 29.09 | 28.59 | 27.78 |
| 9 | 29.09 | 29.63 | 30.24 | 30.82 | 31.14 | 31.26 | 31.20 | 31.22 | 33.00 | 35.65 | 34.67 | 34.26 | 33.66 | 32.70 |
| 10 | 32.03 | 32.97 | 33.89 | 34.77 | 35.37 | 35.75 | 35.81 | 35.87 | 37.99 | 41.09 | 40.01 | 39.56 | 38.89 | 37.79 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 46.142 | 40.013 |
| SC2 | 0 | 8 | 30.552 | 26.595 |
| SC3 | -18 | 7 | 25.659 | 22.459 |
| SC4 | -25 | 6 | 20.725 | 18.217 |
| SC5 | -34 | 6 | 20.766 | 18.436 |
| A | 3025 mm |
|---|---|
| B | 900 mm |
| C | 1260 mm |
| F | 860 mm |
| G | 1585 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3025 mm |
|---|---|
| Width | 1585 mm |
| Height | 1260 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.