Skip to Content

Unit cooler EA-DV-263GC4-A13 C

Unit cooler EA-DV-263GC4-A13 C
Illustrative photo

Producer: Karyer · Line: EA-DV (Cold Store)

Product code: EA-DV-263GC4-A13 C

Cooling capacity i
47.85 kW
Air flow
36,777 m³/h
Fin spacing
4.6 mm
Fans
2 × ⌀630 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA-DV — EA-DV - cold-store evaporator, fans at 90° to the coil, facing the floor
  • B
    Number of fans: 2 — Number of fans (one digit).
  • C
    Fan diameter: 63 — Ø630 mm
  • D
    Dimensional data - coil size letter: G — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: C — 4 tube rows
  • F
    Fin spacing: 4 — Fin spacing about 4 mm
  • G
    Generation code: A — Generation A
  • H
    Fan data: 13 — Ø630: 400V/3Ph/50Hz, 4-pole

Data

Evaporator
Air flow 36,777 m³/h
External surface 216.9 m²
Inner volume 43.4 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 441 kg
Fans
Quantity 2
Diameter 630 mm
Speed 1,330 rpm
Power 5,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 68.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet Ø28
Outlet Ø54
Defrost
EA-DV-263GC4-A13 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
46.021 kW
Low speed (Y)
40.243 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 18.28 18.24 18.22 18.29 18.27 18.20 18.11 18.20 19.27 20.84 20.38 20.21 19.97 19.61
5 23.99 24.34 24.64 24.91 24.97 24.90 24.74 24.81 26.28 28.37 27.66 27.41 27.04 26.50
6 29.47 30.22 31.02 31.68 32.02 32.10 32.02 32.10 34.00 36.74 35.76 35.40 34.87 34.07
7 33.87 35.26 36.53 37.67 38.42 38.89 39.15 39.49 41.94 45.51 44.53 44.07 43.39 42.33
8 38.03 40.03 41.84 43.43 44.50 45.19 45.59 46.02 48.88 53.06 51.98 51.54 50.90 49.85
9 41.86 44.53 46.95 49.06 50.54 51.51 52.10 52.65 55.94 60.75 59.53 59.03 58.28 57.05
10 45.36 48.76 51.85 54.56 56.50 57.81 58.63 59.34 63.07 68.55 67.21 66.65 65.80 64.38

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 16.14 16.04 16.03 16.09 16.09 16.05 16.00 16.14 17.11 18.53 18.15 18.02 17.82 17.53
5 21.22 21.33 21.48 21.65 21.66 21.61 21.51 21.61 22.91 24.79 24.21 24.00 23.71 23.28
6 26.14 26.64 27.10 27.42 27.60 27.62 27.53 27.61 29.26 31.62 30.82 30.52 30.09 29.45
7 30.58 31.53 32.43 33.27 33.76 33.93 33.92 34.03 36.05 38.98 37.96 37.57 37.00 36.10
8 34.48 35.89 37.18 38.36 39.14 39.63 39.91 40.24 42.73 46.38 45.42 45.03 44.33 43.19
9 38.11 40.05 41.82 43.38 44.45 45.14 45.54 45.95 48.80 52.98 51.88 51.42 50.74 49.62
10 41.46 43.99 46.29 48.31 49.72 50.64 51.20 51.72 54.94 59.66 58.44 57.92 57.14 55.83

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 67.21058.443
SC2 0 8 46.02140.243
SC3 -18 7 38.01433.515
SC4 -25 6 31.01727.101
SC5 -34 6 29.54826.282

Dimensions

Dimension drawing of EA-DV-263GC4-A13 C
Dimension drawing
Dimensions as drawn
A 3025 mm
B 900 mm
C 1260 mm
F 860 mm
G 1585 mm
E1 1318 mm
E 2635 mm
D IN 1 x Ø28
D OUT 1 x Ø54
Overall [mm]
Length 3025 mm
Width 1585 mm
Height 1260 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.