EA-DV-163GI4-A13 C
43.30 kW
Defrost: None
Product code: EA-DV-280GC10-A01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 44,136 m³/h |
|---|---|
| External surface | 127.0 m² |
| Inner volume | 53.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 598 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 3,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-DV-280GC10-A01 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.92 | 15.58 | 15.37 | 15.25 | 15.09 | 14.91 | 14.73 | 14.75 | 15.58 | 16.80 | 16.34 | 16.17 | 15.94 | 15.59 |
| 5 | 21.43 | 21.15 | 21.05 | 21.00 | 20.84 | 20.62 | 20.35 | 20.36 | 21.54 | 23.21 | 22.54 | 22.28 | 21.91 | 21.36 |
| 6 | 26.84 | 26.90 | 27.01 | 27.14 | 27.07 | 26.85 | 26.56 | 26.54 | 28.07 | 30.24 | 29.30 | 28.96 | 28.47 | 27.73 |
| 7 | 32.05 | 32.53 | 32.98 | 33.39 | 33.44 | 33.36 | 33.11 | 33.12 | 35.01 | 37.75 | 36.58 | 36.13 | 35.49 | 34.48 |
| 8 | 36.97 | 37.79 | 38.70 | 39.49 | 39.90 | 40.01 | 39.88 | 39.94 | 42.27 | 45.63 | 44.26 | 43.72 | 42.93 | 41.66 |
| 9 | 41.04 | 42.46 | 43.79 | 45.02 | 45.83 | 46.31 | 46.54 | 46.89 | 49.68 | 53.72 | 52.20 | 51.59 | 50.68 | 49.20 |
| 10 | 44.98 | 46.92 | 48.72 | 50.34 | 51.43 | 52.12 | 52.48 | 52.92 | 56.17 | 60.94 | 59.58 | 59.01 | 58.17 | 56.77 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 13.74 | 13.42 | 13.24 | 13.15 | 13.05 | 12.93 | 12.80 | 12.91 | 13.66 | 14.76 | 14.40 | 14.27 | 14.09 | 13.82 |
| 5 | 18.33 | 18.06 | 17.93 | 17.87 | 17.75 | 17.58 | 17.38 | 17.47 | 18.50 | 19.98 | 19.45 | 19.26 | 19.00 | 18.61 |
| 6 | 23.04 | 22.90 | 22.85 | 22.90 | 22.81 | 22.64 | 22.40 | 22.45 | 23.76 | 25.63 | 24.88 | 24.60 | 24.22 | 23.64 |
| 7 | 27.60 | 27.71 | 27.90 | 28.11 | 28.12 | 27.97 | 27.73 | 27.75 | 29.36 | 31.67 | 30.70 | 30.33 | 29.81 | 28.99 |
| 8 | 31.98 | 32.44 | 32.90 | 33.35 | 33.52 | 33.43 | 33.24 | 33.27 | 35.19 | 37.98 | 36.81 | 36.36 | 35.70 | 34.63 |
| 9 | 36.15 | 36.89 | 37.71 | 38.46 | 38.86 | 38.97 | 38.87 | 38.93 | 41.20 | 44.52 | 43.19 | 42.66 | 41.86 | 40.59 |
| 10 | 39.74 | 40.98 | 42.17 | 43.29 | 44.03 | 44.46 | 44.54 | 44.68 | 47.32 | 51.16 | 49.71 | 49.11 | 48.22 | 46.74 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 59.576 | 49.713 |
| SC2 | 0 | 8 | 39.938 | 33.265 |
| SC3 | -18 | 7 | 33.471 | 28.135 |
| SC4 | -25 | 6 | 27.012 | 22.845 |
| SC5 | -34 | 6 | 26.890 | 23.037 |
| A | 3025 mm |
|---|---|
| B | 900 mm |
| C | 1460 mm |
| F | 860 mm |
| G | 1705 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 3025 mm |
|---|---|
| Width | 1705 mm |
| Height | 1460 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.