EA-130AE10-C05 C
1.98 kW
Defrost: None
Product code: EA-130BC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,490 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 6.4 m² |
| Inner volume | 3.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 24 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.8 dB(A) |
| Energy class | B |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EA-130BC10-C01 C | None |
|---|---|
| EA-130BC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.77 | 0.75 | 0.74 | 0.73 | 0.73 | 0.72 | 0.72 | 0.72 | 0.77 | 0.83 | 0.81 | 0.80 | 0.79 | 0.78 |
| 5 | 1.04 | 1.02 | 1.01 | 1.01 | 1.00 | 0.99 | 0.98 | 0.98 | 1.04 | 1.13 | 1.10 | 1.09 | 1.08 | 1.06 |
| 6 | 1.31 | 1.30 | 1.30 | 1.30 | 1.29 | 1.28 | 1.27 | 1.27 | 1.35 | 1.46 | 1.42 | 1.40 | 1.38 | 1.35 |
| 7 | 1.59 | 1.59 | 1.59 | 1.60 | 1.60 | 1.60 | 1.59 | 1.59 | 1.68 | 1.81 | 1.76 | 1.74 | 1.71 | 1.67 |
| 8 | 1.86 | 1.87 | 1.89 | 1.91 | 1.92 | 1.92 | 1.91 | 1.92 | 2.03 | 2.19 | 2.13 | 2.10 | 2.06 | 2.01 |
| 9 | 2.13 | 2.16 | 2.19 | 2.23 | 2.25 | 2.26 | 2.25 | 2.26 | 2.39 | 2.58 | 2.51 | 2.48 | 2.43 | 2.36 |
| 10 | 2.38 | 2.43 | 2.49 | 2.54 | 2.57 | 2.59 | 2.59 | 2.60 | 2.76 | 2.98 | 2.90 | 2.87 | 2.82 | 2.74 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 2.902 |
| SC2 | 0 | 8 | 1.915 |
| SC3 | -18 | 7 | 1.604 |
| SC4 | -25 | 6 | 1.296 |
| SC5 | -34 | 6 | 1.312 |
| A | 907 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E | 585 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 907 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.