EA-140AC10-C01 C
3.53 kW
Defrost: None
Product code: EA-135AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,298 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 10.5 m² |
| Inner volume | 4.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 34 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-135AE10-C01 C | None |
|---|---|
| EA-135AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.35 | 1.32 | 1.30 | 1.29 | 1.28 | 1.26 | 1.25 | 1.27 | 1.35 | 1.45 | 1.42 | 1.41 | 1.39 | 1.36 |
| 5 | 1.82 | 1.80 | 1.79 | 1.78 | 1.77 | 1.75 | 1.72 | 1.74 | 1.85 | 2.00 | 1.95 | 1.93 | 1.90 | 1.87 |
| 6 | 2.29 | 2.29 | 2.30 | 2.31 | 2.30 | 2.28 | 2.25 | 2.26 | 2.40 | 2.59 | 2.51 | 2.48 | 2.44 | 2.38 |
| 7 | 2.75 | 2.78 | 2.81 | 2.85 | 2.85 | 2.84 | 2.81 | 2.82 | 2.99 | 3.22 | 3.11 | 3.07 | 3.01 | 2.92 |
| 8 | 3.21 | 3.28 | 3.33 | 3.39 | 3.42 | 3.42 | 3.39 | 3.40 | 3.60 | 3.89 | 3.75 | 3.70 | 3.62 | 3.49 |
| 9 | 3.63 | 3.75 | 3.85 | 3.94 | 3.99 | 4.00 | 3.98 | 4.00 | 4.24 | 4.57 | 4.42 | 4.36 | 4.27 | 4.11 |
| 10 | 4.03 | 4.19 | 4.34 | 4.48 | 4.55 | 4.59 | 4.59 | 4.61 | 4.88 | 5.28 | 5.11 | 5.04 | 4.93 | 4.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.113 |
| SC2 | 0 | 8 | 3.404 |
| SC3 | -18 | 7 | 2.852 |
| SC4 | -25 | 6 | 2.296 |
| SC5 | -34 | 6 | 2.291 |
| A | 857 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E | 535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 857 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.