EA-230AC8-C01 C
3.52 kW
Defrost: None
Product code: EA-230BC10-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,613 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 11.5 m² |
| Inner volume | 4.8 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 32 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-230BC10-C05 C | None |
|---|---|
| EA-230BC10-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.33 | 1.29 | 1.28 | 1.27 | 1.25 | 1.24 | 1.23 | 1.24 | 1.31 | 1.42 | 1.38 | 1.37 | 1.35 | 1.33 |
| 5 | 1.79 | 1.77 | 1.75 | 1.75 | 1.73 | 1.72 | 1.70 | 1.70 | 1.80 | 1.95 | 1.90 | 1.88 | 1.85 | 1.81 |
| 6 | 2.27 | 2.26 | 2.25 | 2.26 | 2.25 | 2.24 | 2.21 | 2.22 | 2.35 | 2.53 | 2.46 | 2.43 | 2.39 | 2.33 |
| 7 | 2.74 | 2.75 | 2.77 | 2.79 | 2.80 | 2.79 | 2.77 | 2.77 | 2.93 | 3.17 | 3.07 | 3.03 | 2.98 | 2.90 |
| 8 | 3.21 | 3.24 | 3.28 | 3.33 | 3.36 | 3.36 | 3.35 | 3.35 | 3.55 | 3.83 | 3.72 | 3.67 | 3.60 | 3.49 |
| 9 | 3.65 | 3.72 | 3.80 | 3.88 | 3.92 | 3.94 | 3.94 | 3.95 | 4.18 | 4.52 | 4.39 | 4.34 | 4.26 | 4.12 |
| 10 | 4.06 | 4.18 | 4.30 | 4.41 | 4.48 | 4.52 | 4.53 | 4.55 | 4.83 | 5.22 | 5.08 | 5.02 | 4.93 | 4.77 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.084 |
| SC2 | 0 | 8 | 3.351 |
| SC3 | -18 | 7 | 2.797 |
| SC4 | -25 | 6 | 2.254 |
| SC5 | -34 | 6 | 2.268 |
| A | 1357 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1357 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.