EA-230BE10-C05 C
4.58 kW
Defrost: None
Product code: EA-135AE6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,114 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 16.4 m² |
| Inner volume | 4.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 35 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-135AE6-C01 C | None |
|---|---|
| EA-135AE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.75 | 1.74 | 1.74 | 1.74 | 1.74 | 1.73 | 1.71 | 1.76 | 1.88 | 2.04 | 2.00 | 1.98 | 1.96 | 1.93 |
| 5 | 2.30 | 2.31 | 2.32 | 2.34 | 2.34 | 2.33 | 2.31 | 2.35 | 2.49 | 2.70 | 2.63 | 2.61 | 2.58 | 2.54 |
| 6 | 2.83 | 2.88 | 2.93 | 2.97 | 2.99 | 2.98 | 2.95 | 2.98 | 3.16 | 3.42 | 3.32 | 3.28 | 3.22 | 3.14 |
| 7 | 3.36 | 3.45 | 3.54 | 3.61 | 3.64 | 3.65 | 3.62 | 3.65 | 3.87 | 4.18 | 4.04 | 3.99 | 3.91 | 3.78 |
| 8 | 3.84 | 3.99 | 4.13 | 4.25 | 4.32 | 4.34 | 4.31 | 4.34 | 4.60 | 4.97 | 4.81 | 4.74 | 4.64 | 4.48 |
| 9 | 4.28 | 4.48 | 4.67 | 4.83 | 4.94 | 4.99 | 5.00 | 5.04 | 5.34 | 5.77 | 5.59 | 5.51 | 5.39 | 5.19 |
| 10 | 4.67 | 4.93 | 5.17 | 5.36 | 5.50 | 5.58 | 5.61 | 5.68 | 6.02 | 6.52 | 6.36 | 6.27 | 6.16 | 5.91 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.355 |
| SC2 | 0 | 8 | 4.343 |
| SC3 | -18 | 7 | 3.626 |
| SC4 | -25 | 6 | 2.927 |
| SC5 | -34 | 6 | 2.843 |
| A | 857 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E | 535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 857 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.