EA-230BC7-C01 C
4.45 kW
Defrost: None
Product code: EA-230AE7-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,961 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 19.1 m² |
| Inner volume | 6.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 32 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-230AE7-C05 C | None |
|---|---|
| EA-230AE7-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.76 | 1.76 | 1.77 | 1.79 | 1.79 | 1.78 | 1.77 | 1.82 | 1.94 | 2.11 | 2.08 | 2.06 | 2.05 | 2.03 |
| 5 | 2.27 | 2.30 | 2.34 | 2.37 | 2.38 | 2.37 | 2.35 | 2.40 | 2.55 | 2.77 | 2.69 | 2.67 | 2.63 | 2.58 |
| 6 | 2.77 | 2.84 | 2.91 | 2.97 | 2.99 | 3.00 | 2.97 | 3.01 | 3.20 | 3.46 | 3.35 | 3.31 | 3.25 | 3.16 |
| 7 | 3.26 | 3.37 | 3.48 | 3.56 | 3.61 | 3.63 | 3.61 | 3.65 | 3.87 | 4.19 | 4.05 | 3.99 | 3.91 | 3.78 |
| 8 | 3.71 | 3.87 | 4.03 | 4.16 | 4.24 | 4.27 | 4.26 | 4.30 | 4.56 | 4.93 | 4.77 | 4.71 | 4.61 | 4.45 |
| 9 | 4.11 | 4.33 | 4.54 | 4.72 | 4.83 | 4.90 | 4.91 | 4.95 | 5.24 | 5.67 | 5.50 | 5.43 | 5.32 | 5.12 |
| 10 | 4.48 | 4.76 | 5.01 | 5.24 | 5.37 | 5.46 | 5.49 | 5.57 | 5.90 | 6.39 | 6.23 | 6.16 | 6.03 | 5.81 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.234 |
| SC2 | 0 | 8 | 4.300 |
| SC3 | -18 | 7 | 3.587 |
| SC4 | -25 | 6 | 2.905 |
| SC5 | -34 | 6 | 2.788 |
| A | 1157 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 417.5 mm |
| E | 835 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1157 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.