EA-140AE10-C01 C
4.88 kW
Defrost: None
Product code: EA-135AG4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,742 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 30.4 m² |
| Inner volume | 6.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 44 kg |
| Quantity | 1 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 165 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.2 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-135AG4-C01 C | None |
|---|---|
| EA-135AG4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.96 | 1.99 | 2.03 | 2.06 | 2.07 | 2.07 | 2.05 | 2.13 | 2.28 | 2.48 | 2.44 | 2.42 | 2.41 | 2.39 |
| 5 | 2.47 | 2.55 | 2.61 | 2.67 | 2.70 | 2.70 | 2.67 | 2.74 | 2.92 | 3.17 | 3.08 | 3.05 | 3.00 | 2.93 |
| 6 | 2.96 | 3.08 | 3.20 | 3.29 | 3.34 | 3.35 | 3.33 | 3.38 | 3.59 | 3.89 | 3.76 | 3.70 | 3.63 | 3.50 |
| 7 | 3.44 | 3.62 | 3.78 | 3.92 | 3.99 | 4.01 | 3.99 | 4.04 | 4.28 | 4.63 | 4.47 | 4.40 | 4.29 | 4.11 |
| 8 | 3.86 | 4.11 | 4.32 | 4.51 | 4.63 | 4.68 | 4.66 | 4.71 | 4.99 | 5.39 | 5.20 | 5.11 | 4.97 | 4.75 |
| 9 | 4.23 | 4.54 | 4.82 | 5.06 | 5.19 | 5.27 | 5.29 | 5.36 | 5.67 | 6.13 | 5.93 | 5.83 | 5.67 | 5.41 |
| 10 | 4.57 | 4.94 | 5.29 | 5.55 | 5.76 | 5.87 | 5.90 | 5.98 | 6.33 | 6.84 | 6.64 | 6.53 | 6.36 | 6.07 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.636 |
| SC2 | 0 | 8 | 4.710 |
| SC3 | -18 | 7 | 3.955 |
| SC4 | -25 | 6 | 3.197 |
| SC5 | -34 | 6 | 2.991 |
| A | 857 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E | 535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 857 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.