EA-135AG4-C01 C
4.89 kW
Defrost: None
Product code: EA-140AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,042 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 13.4 m² |
| Inner volume | 6.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 41 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 160 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-140AE10-C01 C | None |
|---|---|
| EA-140AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.78 | 1.77 | 1.78 | 1.78 | 1.77 | 1.76 | 1.73 | 1.77 | 1.87 | 2.02 | 1.97 | 1.95 | 1.92 | 1.88 |
| 5 | 2.34 | 2.37 | 2.41 | 2.44 | 2.44 | 2.43 | 2.40 | 2.44 | 2.59 | 2.80 | 2.72 | 2.69 | 2.66 | 2.60 |
| 6 | 2.88 | 2.97 | 3.04 | 3.11 | 3.14 | 3.14 | 3.12 | 3.16 | 3.35 | 3.62 | 3.51 | 3.47 | 3.41 | 3.32 |
| 7 | 3.42 | 3.56 | 3.68 | 3.79 | 3.85 | 3.88 | 3.87 | 3.91 | 4.14 | 4.48 | 4.34 | 4.29 | 4.21 | 4.07 |
| 8 | 3.89 | 4.10 | 4.29 | 4.45 | 4.56 | 4.62 | 4.63 | 4.68 | 4.96 | 5.37 | 5.21 | 5.14 | 5.04 | 4.87 |
| 9 | 4.31 | 4.57 | 4.82 | 5.04 | 5.17 | 5.26 | 5.31 | 5.40 | 5.73 | 6.23 | 6.08 | 6.01 | 5.90 | 5.70 |
| 10 | 4.68 | 5.02 | 5.33 | 5.57 | 5.77 | 5.90 | 5.97 | 6.07 | 6.45 | 7.01 | 6.86 | 6.78 | 6.67 | 6.47 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.856 |
| SC2 | 0 | 8 | 4.675 |
| SC3 | -18 | 7 | 3.815 |
| SC4 | -25 | 6 | 3.044 |
| SC5 | -34 | 6 | 2.905 |
| A | 917 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E | 585 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 917 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.