EA-630BC7-C01 C
11.32 kW
Defrost: Electric
Product code: EA-150AG10-C09 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,184 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 31.6 m² |
| Inner volume | 14.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 79 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 710 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-150AG10-C09 C | None |
|---|---|
| EA-150AG10-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.20 | 4.17 | 4.16 | 4.16 | 4.13 | 4.09 | 4.03 | 4.11 | 4.36 | 4.71 | 4.58 | 4.53 | 4.46 | 4.36 |
| 5 | 5.54 | 5.59 | 5.65 | 5.70 | 5.70 | 5.66 | 5.59 | 5.66 | 6.00 | 6.49 | 6.29 | 6.23 | 6.15 | 6.02 |
| 6 | 6.84 | 7.00 | 7.15 | 7.28 | 7.33 | 7.32 | 7.26 | 7.32 | 7.76 | 8.38 | 8.11 | 8.01 | 7.87 | 7.65 |
| 7 | 8.12 | 8.40 | 8.66 | 8.88 | 8.99 | 9.03 | 8.99 | 9.06 | 9.60 | 10.38 | 10.05 | 9.91 | 9.72 | 9.40 |
| 8 | 9.27 | 9.69 | 10.08 | 10.43 | 10.66 | 10.76 | 10.76 | 10.84 | 11.49 | 12.44 | 12.06 | 11.91 | 11.66 | 11.25 |
| 9 | 10.27 | 10.83 | 11.35 | 11.81 | 12.07 | 12.27 | 12.36 | 12.53 | 13.30 | 14.44 | 14.09 | 13.91 | 13.63 | 13.15 |
| 10 | 11.18 | 11.90 | 12.57 | 13.07 | 13.49 | 13.76 | 13.90 | 14.10 | 14.97 | 16.25 | 15.89 | 15.71 | 15.44 | 14.96 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.888 |
| SC2 | 0 | 8 | 10.842 |
| SC3 | -18 | 7 | 8.924 |
| SC4 | -25 | 6 | 7.150 |
| SC5 | -34 | 6 | 6.885 |
| A | 1237 mm |
|---|---|
| B | 740 mm |
| C | 685 mm |
| F | 545 mm |
| E | 885 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 1237 mm |
|---|---|
| Width | 690 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.