EA-163FD7-C19 C
15.16 kW
Defrost: Electric
Product code: EA-163EE4-C01 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,448 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 100.2 m² |
| Inner volume | 20.4 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 127 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-163EE4-C01 C | None |
|---|---|
| EA-163EE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.89 | 5.95 | 6.02 | 6.10 | 6.13 | 6.13 | 6.11 | 6.27 | 6.69 | 7.27 | 7.16 | 7.12 | 7.06 | 6.96 |
| 5 | 7.57 | 7.74 | 7.89 | 8.03 | 8.09 | 8.10 | 8.06 | 8.21 | 8.73 | 9.48 | 9.26 | 9.19 | 9.09 | 8.94 |
| 6 | 9.14 | 9.47 | 9.77 | 10.02 | 10.15 | 10.16 | 10.13 | 10.26 | 10.89 | 11.81 | 11.50 | 11.38 | 11.21 | 10.95 |
| 7 | 10.60 | 11.07 | 11.54 | 11.94 | 12.18 | 12.29 | 12.28 | 12.42 | 13.17 | 14.27 | 13.87 | 13.71 | 13.48 | 13.10 |
| 8 | 11.85 | 12.55 | 13.18 | 13.74 | 14.12 | 14.34 | 14.43 | 14.63 | 15.52 | 16.82 | 16.35 | 16.15 | 15.86 | 15.37 |
| 9 | 12.98 | 13.88 | 14.71 | 15.43 | 15.93 | 16.23 | 16.37 | 16.60 | 17.63 | 19.14 | 18.69 | 18.49 | 18.18 | 17.67 |
| 10 | ≈ 14.01 | 15.13 | 16.17 | 17.07 | 17.70 | 18.11 | 18.32 | 18.59 | 19.74 | 21.43 | 20.94 | 20.71 | 20.35 | 19.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.935 |
| SC2 | 0 | 8 | 14.625 |
| SC3 | -18 | 7 | 12.052 |
| SC4 | -25 | 6 | 9.771 |
| SC5 | -34 | 6 | 9.225 |
| A | 1215 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E | 835 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 1215 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.