EA-530AE4-C05 C
12.15 kW
Defrost: None
Product code: EA-163FC10-C08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,383 m³/h |
|---|---|
| Air throw | 38 m |
| External surface | 40.7 m² |
| Inner volume | 17.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 128 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 1,900 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 70.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | E |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-163FC10-C08 C | None |
|---|---|
| EA-163FC10-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.51 | 4.40 | 4.33 | 4.29 | 4.23 | 4.18 | 4.13 | 4.12 | 4.35 | 4.69 | 4.56 | 4.52 | 4.45 | 4.36 |
| 5 | 6.11 | 6.04 | 5.99 | 5.96 | 5.90 | 5.82 | 5.74 | 5.73 | 6.05 | 6.51 | 6.31 | 6.23 | 6.13 | 5.97 |
| 6 | 7.75 | 7.76 | 7.77 | 7.78 | 7.73 | 7.66 | 7.56 | 7.53 | 7.96 | 8.56 | 8.29 | 8.19 | 8.05 | 7.83 |
| 7 | 9.31 | 9.45 | 9.56 | 9.67 | 9.68 | 9.63 | 9.53 | 9.50 | 10.04 | 10.80 | 10.45 | 10.32 | 10.13 | 9.83 |
| 8 | 10.78 | 11.08 | 11.29 | 11.51 | 11.61 | 11.62 | 11.57 | 11.55 | 12.22 | 13.17 | 12.75 | 12.58 | 12.35 | 11.98 |
| 9 | 12.06 | 12.50 | 12.91 | 13.28 | 13.52 | 13.66 | 13.65 | 13.67 | 14.47 | 15.63 | 15.16 | 14.98 | 14.71 | 14.27 |
| 10 | 13.21 | 13.82 | 14.37 | 14.87 | 15.20 | 15.40 | 15.51 | 15.64 | 16.60 | 18.00 | 17.60 | 17.43 | 17.13 | 16.64 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.06 | 3.96 | 3.90 | 3.86 | 3.83 | 3.79 | 3.75 | 3.76 | 3.97 | 4.29 | 4.18 | 4.14 | 4.09 | 4.01 |
| 5 | 5.48 | 5.39 | 5.34 | 5.31 | 5.26 | 5.20 | 5.14 | 5.14 | 5.44 | 5.87 | 5.70 | 5.64 | 5.55 | 5.43 |
| 6 | 6.94 | 6.90 | 6.87 | 6.88 | 6.84 | 6.77 | 6.69 | 6.68 | 7.07 | 7.61 | 7.38 | 7.30 | 7.18 | 7.01 |
| 7 | 8.35 | 8.41 | 8.46 | 8.52 | 8.51 | 8.45 | 8.37 | 8.35 | 8.83 | 9.51 | 9.21 | 9.10 | 8.94 | 8.69 |
| 8 | 9.71 | 9.88 | 10.04 | 10.18 | 10.23 | 10.20 | 10.13 | 10.10 | 10.68 | 11.52 | 11.15 | 11.01 | 10.81 | 10.49 |
| 9 | 10.99 | 11.31 | 11.55 | 11.79 | 11.92 | 11.95 | 11.91 | 11.92 | 12.61 | 13.61 | 13.19 | 13.02 | 12.78 | 12.39 |
| 10 | 12.10 | 12.54 | 12.95 | 13.33 | 13.58 | 13.73 | 13.73 | 13.77 | 14.57 | 15.75 | 15.30 | 15.11 | 14.84 | 14.38 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 17.602 | 15.295 |
| SC2 | 0 | 8 | 11.552 | 10.100 |
| SC3 | -18 | 7 | 9.679 | 8.524 |
| SC4 | -25 | 6 | 7.769 | 6.874 |
| SC5 | -34 | 6 | 7.762 | 6.941 |
| A | 1415 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| G | 935 mm |
| E | 1035 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 1415 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.