EA-130BE4-C01 C
3.35 kW
Defrost: None
Product code: EA-230AC7-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,277 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 12.6 m² |
| Inner volume | 3.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 26 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø22 |
| EA-230AC7-C05 C | None |
|---|---|
| EA-230AC7-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.30 | 1.26 | 1.24 | 1.24 | 1.22 | 1.21 | 1.20 | 1.23 | 1.30 | 1.41 | 1.38 | 1.37 | 1.36 | 1.34 |
| 5 | 1.77 | 1.73 | 1.71 | 1.70 | 1.68 | 1.66 | 1.64 | 1.66 | 1.76 | 1.91 | 1.86 | 1.85 | 1.83 | 1.80 |
| 6 | 2.25 | 2.23 | 2.21 | 2.21 | 2.19 | 2.16 | 2.13 | 2.14 | 2.27 | 2.45 | 2.38 | 2.35 | 2.32 | 2.27 |
| 7 | 2.75 | 2.74 | 2.74 | 2.74 | 2.73 | 2.71 | 2.67 | 2.68 | 2.83 | 3.05 | 2.95 | 2.91 | 2.86 | 2.78 |
| 8 | 3.24 | 3.25 | 3.27 | 3.30 | 3.30 | 3.28 | 3.24 | 3.24 | 3.43 | 3.69 | 3.56 | 3.51 | 3.43 | 3.32 |
| 9 | 3.71 | 3.76 | 3.82 | 3.87 | 3.88 | 3.87 | 3.83 | 3.83 | 4.05 | 4.37 | 4.21 | 4.15 | 4.05 | 3.90 |
| 10 | 4.14 | 4.24 | 4.33 | 4.43 | 4.47 | 4.47 | 4.44 | 4.45 | 4.70 | 5.07 | 4.89 | 4.81 | 4.70 | 4.52 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.891 |
| SC2 | 0 | 8 | 3.241 |
| SC3 | -18 | 7 | 2.741 |
| SC4 | -25 | 6 | 2.211 |
| SC5 | -34 | 6 | 2.251 |
| A | 1157 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 417.5 mm |
| E | 835 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø22 |
| Length | 1157 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.