EA-230BC6-C01 C
4.76 kW
Defrost: None
Product code: EA-230AE4-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,784 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 30.4 m² |
| Inner volume | 6.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 32 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-230AE4-C05 C | None |
|---|---|
| EA-230AE4-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.92 | 1.93 | 1.96 | 1.98 | 1.99 | 1.99 | 1.98 | 2.04 | 2.18 | 2.37 | 2.33 | 2.32 | 2.30 | 2.29 |
| 5 | 2.44 | 2.49 | 2.54 | 2.58 | 2.61 | 2.61 | 2.59 | 2.64 | 2.81 | 3.05 | 2.97 | 2.95 | 2.91 | 2.85 |
| 6 | 2.94 | 3.03 | 3.12 | 3.19 | 3.24 | 3.25 | 3.23 | 3.27 | 3.47 | 3.77 | 3.65 | 3.61 | 3.54 | 3.44 |
| 7 | 3.44 | 3.57 | 3.70 | 3.81 | 3.87 | 3.90 | 3.88 | 3.92 | 4.16 | 4.50 | 4.36 | 4.30 | 4.22 | 4.07 |
| 8 | 3.88 | 4.08 | 4.26 | 4.42 | 4.51 | 4.55 | 4.55 | 4.59 | 4.86 | 5.26 | 5.10 | 5.03 | 4.91 | 4.73 |
| 9 | 4.27 | 4.53 | 4.76 | 4.97 | 5.10 | 5.16 | 5.18 | 5.24 | 5.56 | 6.02 | 5.84 | 5.75 | 5.62 | 5.40 |
| 10 | 4.63 | 4.95 | 5.25 | 5.47 | 5.65 | 5.75 | 5.79 | 5.86 | 6.21 | 6.73 | 6.55 | 6.46 | 6.32 | 6.08 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.548 |
| SC2 | 0 | 8 | 4.590 |
| SC3 | -18 | 7 | 3.836 |
| SC4 | -25 | 6 | 3.117 |
| SC5 | -34 | 6 | 2.963 |
| A | 1157 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 417.5 mm |
| E | 835 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1157 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.