EA-230BC6-C01 C
4.76 kW
Defrost: None
Product code: EA-230BE8-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,296 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 21.0 m² |
| Inner volume | 7.6 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 38 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-230BE8-C05 C | None |
|---|---|
| EA-230BE8-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.89 | 1.86 | 1.85 | 1.85 | 1.84 | 1.83 | 1.82 | 1.86 | 1.98 | 2.15 | 2.11 | 2.10 | 2.08 | 2.04 |
| 5 | 2.48 | 2.47 | 2.47 | 2.48 | 2.48 | 2.46 | 2.44 | 2.47 | 2.62 | 2.84 | 2.77 | 2.75 | 2.71 | 2.67 |
| 6 | 3.08 | 3.09 | 3.11 | 3.14 | 3.14 | 3.13 | 3.10 | 3.13 | 3.32 | 3.59 | 3.48 | 3.44 | 3.39 | 3.30 |
| 7 | 3.66 | 3.71 | 3.76 | 3.81 | 3.83 | 3.83 | 3.80 | 3.82 | 4.05 | 4.38 | 4.24 | 4.18 | 4.10 | 3.97 |
| 8 | 4.24 | 4.33 | 4.40 | 4.49 | 4.53 | 4.54 | 4.51 | 4.54 | 4.80 | 5.19 | 5.03 | 4.96 | 4.85 | 4.67 |
| 9 | 4.78 | 4.91 | 5.05 | 5.17 | 5.23 | 5.25 | 5.24 | 5.27 | 5.58 | 6.03 | 5.84 | 5.76 | 5.63 | 5.42 |
| 10 | 5.29 | 5.48 | 5.67 | 5.83 | 5.93 | 5.98 | 5.97 | 6.01 | 6.37 | 6.88 | 6.68 | 6.58 | 6.43 | 6.18 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.675 |
| SC2 | 0 | 8 | 4.538 |
| SC3 | -18 | 7 | 3.823 |
| SC4 | -25 | 6 | 3.111 |
| SC5 | -34 | 6 | 3.085 |
| A | 1357 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1357 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.