EA-630BC4-C01 C
13.83 kW
Defrost: None
Product code: EA-245AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,492 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 38.4 m² |
| Inner volume | 11.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 78 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| EA-245AC6-C01 C | None |
|---|---|
| EA-245AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.95 | 4.98 | 5.00 | 5.02 | 5.00 | 4.95 | 4.89 | 4.96 | 5.24 | 5.64 | 5.49 | 5.43 | 5.35 | 5.23 |
| 5 | 6.60 | 6.76 | 6.87 | 6.98 | 7.02 | 7.00 | 6.93 | 7.02 | 7.45 | 8.04 | 7.82 | 7.74 | 7.64 | 7.46 |
| 6 | 8.11 | 8.43 | 8.72 | 8.99 | 9.16 | 9.21 | 9.16 | 9.27 | 9.83 | 10.61 | 10.31 | 10.20 | 10.04 | 9.80 |
| 7 | 9.35 | 9.84 | 10.28 | 10.62 | 10.88 | 11.05 | 11.13 | 11.30 | 12.02 | 13.06 | 12.79 | 12.69 | 12.53 | 12.27 |
| 8 | 10.50 | 11.10 | 11.71 | 12.24 | 12.63 | 12.87 | 13.01 | 13.22 | 14.06 | 15.29 | 14.97 | 14.84 | 14.65 | 14.33 |
| 9 | 11.42 | 12.33 | 13.12 | 13.83 | 14.34 | 14.69 | 14.90 | 15.15 | 16.12 | 17.54 | 17.19 | 17.04 | 16.82 | 16.43 |
| 10 | 12.42 | 13.47 | 14.47 | 15.36 | 16.02 | 16.49 | 16.78 | 17.09 | 18.19 | 19.81 | 19.44 | 19.27 | 19.02 | 18.57 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.439 |
| SC2 | 0 | 8 | 13.216 |
| SC3 | -18 | 7 | 10.737 |
| SC4 | -25 | 6 | 8.721 |
| SC5 | -34 | 6 | 8.185 |
| A | 1767 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 1767 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.