EA-263EC10-C06 C
17.35 kW
Defrost: None
Product code: EA-245AG10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,187 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 48.9 m² |
| Inner volume | 22.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 110 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-245AG10-C01 C | None |
|---|---|
| EA-245AG10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.46 | 6.46 | 6.48 | 6.50 | 6.47 | 6.41 | 6.32 | 6.48 | 6.90 | 7.47 | 7.27 | 7.20 | 7.09 | 6.94 |
| 5 | 8.47 | 8.59 | 8.72 | 8.83 | 8.86 | 8.82 | 8.72 | 8.86 | 9.41 | 10.18 | 9.89 | 9.79 | 9.66 | 9.48 |
| 6 | 10.45 | 10.68 | 10.97 | 11.21 | 11.33 | 11.34 | 11.25 | 11.39 | 12.07 | 13.06 | 12.64 | 12.49 | 12.26 | 11.90 |
| 7 | 12.25 | 12.75 | 13.21 | 13.60 | 13.83 | 13.90 | 13.86 | 14.00 | 14.84 | 16.07 | 15.56 | 15.36 | 15.05 | 14.55 |
| 8 | 13.89 | 14.58 | 15.23 | 15.81 | 16.19 | 16.42 | 16.45 | 16.65 | 17.64 | 19.11 | 18.55 | 18.31 | 17.94 | 17.32 |
| 9 | 15.33 | 16.25 | 17.10 | 17.77 | 18.28 | 18.60 | 18.75 | 19.03 | 20.21 | 21.94 | 21.42 | 21.18 | 20.80 | 20.13 |
| 10 | 16.66 | 17.82 | 18.79 | 19.72 | 20.39 | 20.83 | 21.05 | 21.38 | 22.71 | 24.66 | 24.09 | 23.82 | 23.40 | 22.62 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.093 |
| SC2 | 0 | 8 | 16.645 |
| SC3 | -18 | 7 | 13.713 |
| SC4 | -25 | 6 | 10.966 |
| SC5 | -34 | 6 | 10.520 |
| A | 1767 mm |
|---|---|
| B | 690 mm |
| C | 645 mm |
| F | 495 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 1767 mm |
|---|---|
| Width | 690 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.