EA-163FE7-C19 C
17.45 kW
Defrost: None
Product code: EA-435AG10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,352 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 55.9 m² |
| Inner volume | 25.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 121 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-435AG10-C01 C | None |
|---|---|
| EA-435AG10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.79 | 6.74 | 6.72 | 6.73 | 6.70 | 6.64 | 6.56 | 6.73 | 7.17 | 7.77 | 7.61 | 7.56 | 7.46 | 7.32 |
| 5 | 8.90 | 8.93 | 9.00 | 9.07 | 9.07 | 9.01 | 8.90 | 9.05 | 9.61 | 10.40 | 10.10 | 10.01 | 9.87 | 9.68 |
| 6 | 10.96 | 11.12 | 11.30 | 11.47 | 11.53 | 11.50 | 11.39 | 11.51 | 12.20 | 13.20 | 12.77 | 12.61 | 12.38 | 12.02 |
| 7 | 13.00 | 13.31 | 13.58 | 13.87 | 14.02 | 14.05 | 13.96 | 14.07 | 14.90 | 16.12 | 15.59 | 15.37 | 15.05 | 14.51 |
| 8 | 14.86 | 15.37 | 15.86 | 16.29 | 16.54 | 16.60 | 16.55 | 16.69 | 17.67 | 19.11 | 18.51 | 18.24 | 17.85 | 17.16 |
| 9 | 16.59 | 17.29 | 17.96 | 18.57 | 18.95 | 19.17 | 19.17 | 19.33 | 20.48 | 22.12 | 21.46 | 21.16 | 20.69 | 19.86 |
| 10 | 18.13 | 19.05 | 19.92 | 20.67 | 21.12 | 21.43 | 21.55 | 21.82 | 23.14 | 25.08 | 24.44 | 24.11 | 23.57 | 22.61 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.440 |
| SC2 | 0 | 8 | 16.687 |
| SC3 | -18 | 7 | 13.948 |
| SC4 | -25 | 6 | 11.298 |
| SC5 | -34 | 6 | 11.007 |
| A | 2357 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2357 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.