20.34 kW
Defrost: None
Product code: EA-245AG6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,352 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 76.7 m² |
| Inner volume | 22.8 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 115 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-245AG6-C01 C | None |
|---|---|
| EA-245AG6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.02 | 8.01 | 8.04 | 8.08 | 8.07 | 8.00 | 7.90 | 8.17 | 8.71 | 9.46 | 9.28 | 9.23 | 9.16 | 9.02 |
| 5 | 10.41 | 10.53 | 10.66 | 10.78 | 10.80 | 10.73 | 10.59 | 10.83 | 11.52 | 12.49 | 12.14 | 12.02 | 11.86 | 11.65 |
| 6 | 12.79 | 13.02 | 13.31 | 13.55 | 13.65 | 13.61 | 13.44 | 13.64 | 14.46 | 15.66 | 15.11 | 14.91 | 14.61 | 14.15 |
| 7 | 14.98 | 15.49 | 15.96 | 16.36 | 16.56 | 16.55 | 16.39 | 16.56 | 17.53 | 18.96 | 18.27 | 17.99 | 17.57 | 16.85 |
| 8 | 16.97 | 17.70 | 18.38 | 18.97 | 19.33 | 19.46 | 19.38 | 19.52 | 20.66 | 22.32 | 21.53 | 21.18 | 20.63 | 19.70 |
| 9 | 18.76 | 19.74 | 20.64 | 21.33 | 21.83 | 22.05 | 22.05 | 22.31 | 23.64 | 25.57 | 24.79 | 24.42 | 23.77 | 22.63 |
| 10 | 20.41 | 21.67 | 22.71 | 23.70 | 24.33 | 24.68 | 24.73 | 25.02 | 26.50 | 28.65 | 27.80 | 27.36 | 26.68 | 25.47 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 27.796 |
| SC2 | 0 | 8 | 19.518 |
| SC3 | -18 | 7 | 16.461 |
| SC4 | -25 | 6 | 13.306 |
| SC5 | -34 | 6 | 12.865 |
| A | 1767 mm |
|---|---|
| B | 690 mm |
| C | 645 mm |
| F | 495 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 1767 mm |
|---|---|
| Width | 690 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.