EA-245AG6-C01 C
20.36 kW
Defrost: None
Product code: EA-440AE8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 11,722 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 64.9 m² |
| Inner volume | 23.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 123 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-440AE8-C01 C | None |
|---|---|
| EA-440AE8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.52 | 7.58 | 7.65 | 7.72 | 7.71 | 7.66 | 7.57 | 7.77 | 8.27 | 8.94 | 8.70 | 8.62 | 8.49 | 8.31 |
| 5 | 9.78 | 10.05 | 10.28 | 10.48 | 10.57 | 10.55 | 10.45 | 10.65 | 11.32 | 12.26 | 11.92 | 11.81 | 11.65 | 11.44 |
| 6 | 12.00 | 12.49 | 12.94 | 13.31 | 13.52 | 13.57 | 13.51 | 13.71 | 14.55 | 15.76 | 15.28 | 15.10 | 14.83 | 14.42 |
| 7 | 13.93 | 14.65 | 15.32 | 15.92 | 16.31 | 16.49 | 16.57 | 16.84 | 17.88 | 19.38 | 18.82 | 18.60 | 18.26 | 17.69 |
| 8 | 15.61 | 16.60 | 17.51 | 18.20 | 18.76 | 19.11 | 19.27 | 19.58 | 20.82 | 22.63 | 22.10 | 21.88 | 21.52 | 20.93 |
| 9 | 17.15 | 18.25 | 19.46 | 20.49 | 21.22 | 21.70 | 21.95 | 22.33 | 23.74 | 25.81 | 25.23 | 24.96 | 24.55 | 23.84 |
| 10 | 18.54 | 19.98 | 21.42 | 22.69 | 23.63 | 24.26 | 24.62 | 25.09 | 26.68 | 29.00 | 28.39 | 28.09 | 27.62 | 26.80 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 28.389 |
| SC2 | 0 | 8 | 19.584 |
| SC3 | -18 | 7 | 16.095 |
| SC4 | -25 | 6 | 12.936 |
| SC5 | -34 | 6 | 12.118 |
| A | 2567 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2235 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 2567 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.