EA-345AC8-C01 C
18.20 kW
Defrost: None
Product code: EA-245AG8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,850 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 59.3 m² |
| Inner volume | 22.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 113 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-245AG8-C01 C | None |
|---|---|
| EA-245AG8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.85 | 6.88 | 6.92 | 6.96 | 6.95 | 6.90 | 6.81 | 7.00 | 7.46 | 8.08 | 7.91 | 7.83 | 7.73 | 7.58 |
| 5 | 8.91 | 9.09 | 9.25 | 9.40 | 9.45 | 9.41 | 9.31 | 9.48 | 10.07 | 10.91 | 10.60 | 10.49 | 10.36 | 10.17 |
| 6 | 10.95 | 11.30 | 11.59 | 11.87 | 12.02 | 12.05 | 11.96 | 12.12 | 12.85 | 13.91 | 13.47 | 13.30 | 13.05 | 12.67 |
| 7 | 12.78 | 13.37 | 13.91 | 14.37 | 14.64 | 14.74 | 14.68 | 14.85 | 15.74 | 17.05 | 16.51 | 16.29 | 15.95 | 15.37 |
| 8 | 14.41 | 15.20 | 15.93 | 16.57 | 17.00 | 17.19 | 17.27 | 17.52 | 18.60 | 20.19 | 19.60 | 19.33 | 18.90 | 18.15 |
| 9 | 15.87 | 16.90 | 17.74 | 18.59 | 19.15 | 19.51 | 19.66 | 19.96 | 21.19 | 23.00 | 22.43 | 22.14 | 21.69 | 20.91 |
| 10 | 17.20 | 18.34 | 19.57 | 20.62 | 21.35 | 21.82 | 22.05 | 22.41 | 23.80 | 25.82 | 25.19 | 24.86 | 24.35 | 23.44 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 25.193 |
| SC2 | 0 | 8 | 17.515 |
| SC3 | -18 | 7 | 14.494 |
| SC4 | -25 | 6 | 11.586 |
| SC5 | -34 | 6 | 11.036 |
| A | 1767 mm |
|---|---|
| B | 690 mm |
| C | 645 mm |
| F | 495 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 1767 mm |
|---|---|
| Width | 690 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.