EA-245AG8-C01 C
18.19 kW
Defrost: None
Product code: EA-345AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,284 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 44.5 m² |
| Inner volume | 17.3 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 109 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-345AC8-C01 C | None |
|---|---|
| EA-345AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.43 | 6.30 | 6.22 | 6.16 | 6.07 | 5.98 | 5.88 | 5.89 | 6.22 | 6.69 | 6.49 | 6.42 | 6.32 | 6.17 |
| 5 | 8.77 | 8.75 | 8.74 | 8.73 | 8.66 | 8.55 | 8.41 | 8.45 | 8.94 | 9.63 | 9.31 | 9.20 | 9.04 | 8.79 |
| 6 | 11.14 | 11.28 | 11.37 | 11.49 | 11.50 | 11.42 | 11.28 | 11.33 | 11.98 | 12.91 | 12.48 | 12.33 | 12.12 | 11.81 |
| 7 | 13.36 | 13.71 | 14.04 | 14.32 | 14.45 | 14.45 | 14.34 | 14.41 | 15.25 | 16.46 | 15.92 | 15.72 | 15.42 | 14.97 |
| 8 | 15.21 | 15.76 | 16.27 | 16.75 | 17.01 | 17.20 | 17.27 | 17.47 | 18.55 | 20.14 | 19.56 | 19.33 | 18.98 | 18.42 |
| 9 | 16.95 | 17.72 | 18.36 | 19.01 | 19.45 | 19.73 | 19.87 | 20.11 | 21.36 | 23.20 | 22.68 | 22.47 | 22.15 | 21.63 |
| 10 | 18.57 | 19.50 | 20.44 | 21.28 | 21.88 | 22.27 | 22.49 | 22.77 | 24.19 | 26.29 | 25.73 | 25.49 | 25.13 | 24.52 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 25.728 |
| SC2 | 0 | 8 | 17.469 |
| SC3 | -18 | 7 | 14.390 |
| SC4 | -25 | 6 | 11.372 |
| SC5 | -34 | 6 | 11.187 |
| A | 2467 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2135 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 2467 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.