EA-250AE4-C10 C
25.63 kW
Defrost: None
Product code: EA-263EE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,922 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 135.2 m² |
| Inner volume | 41.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 203 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.4 dB(A) |
| Energy class | C |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-263EE7-C01 C | None |
|---|---|
| EA-263EE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.06 | 9.99 | 9.98 | 10.02 | 10.00 | 9.96 | 9.90 | 10.10 | 10.74 | 11.63 | 11.39 | 11.31 | 11.18 | 10.99 |
| 5 | 13.18 | 13.18 | 13.27 | 13.37 | 13.38 | 13.32 | 13.22 | 13.41 | 14.24 | 15.43 | 15.07 | 14.94 | 14.77 | 14.51 |
| 6 | 16.20 | 16.44 | 16.68 | 16.90 | 16.98 | 16.93 | 16.81 | 16.97 | 18.00 | 19.47 | 18.94 | 18.75 | 18.47 | 18.06 |
| 7 | 19.09 | 19.60 | 20.07 | 20.47 | 20.67 | 20.65 | 20.55 | 20.70 | 21.93 | 23.72 | 23.03 | 22.77 | 22.38 | 21.77 |
| 8 | 21.79 | 22.53 | 23.28 | 23.93 | 24.30 | 24.45 | 24.40 | 24.57 | 26.03 | 28.17 | 27.34 | 27.01 | 26.51 | 25.72 |
| 9 | 24.12 | 25.24 | 26.27 | 27.20 | 27.80 | 28.16 | 28.30 | 28.51 | 30.22 | 32.71 | 31.78 | 31.39 | 30.80 | 29.84 |
| 10 | 26.28 | 27.74 | 29.08 | 30.27 | 31.05 | 31.53 | 31.76 | 32.12 | 34.10 | 36.99 | 36.12 | 35.74 | 35.16 | 34.05 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 36.119 |
| SC2 | 0 | 8 | 24.565 |
| SC3 | -18 | 7 | 20.575 |
| SC4 | -25 | 6 | 16.679 |
| SC5 | -34 | 6 | 16.274 |
| A | 2015 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E | 1635 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2015 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.