EA-535AG4-C01 C
25.73 kW
Defrost: None
Product code: EA-363EC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 27,129 m³/h |
|---|---|
| Air throw | 24 m |
| External surface | 97.7 m² |
| Inner volume | 41.2 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 242 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 79.6 dB(A) |
| Energy class | D |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø42 |
| EA-363EC10-C01 C | None |
|---|---|
| EA-363EC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.83 | 9.69 | 9.61 | 9.58 | 9.51 | 9.42 | 9.32 | 9.38 | 9.92 | 10.71 | 10.43 | 10.33 | 10.19 | 9.97 |
| 5 | 13.09 | 13.01 | 13.02 | 13.06 | 13.01 | 12.90 | 12.77 | 12.83 | 13.59 | 14.67 | 14.26 | 14.12 | 13.92 | 13.59 |
| 6 | 16.26 | 16.42 | 16.58 | 16.74 | 16.76 | 16.67 | 16.53 | 16.58 | 17.55 | 18.94 | 18.38 | 18.17 | 17.88 | 17.44 |
| 7 | 19.29 | 19.72 | 20.11 | 20.46 | 20.61 | 20.57 | 20.47 | 20.52 | 21.72 | 23.45 | 22.76 | 22.49 | 22.11 | 21.50 |
| 8 | 22.12 | 22.78 | 23.47 | 24.06 | 24.40 | 24.54 | 24.51 | 24.61 | 26.07 | 28.18 | 27.36 | 27.05 | 26.57 | 25.81 |
| 9 | 24.54 | 25.58 | 26.55 | 27.42 | 28.01 | 28.38 | 28.56 | 28.76 | 30.49 | 33.01 | 32.11 | 31.74 | 31.20 | 30.31 |
| 10 | 26.80 | 28.19 | 29.46 | 30.59 | 31.37 | 31.87 | 32.15 | 32.48 | 34.49 | 37.44 | 36.64 | 36.29 | 35.78 | 34.89 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 36.635 |
| SC2 | 0 | 8 | 24.609 |
| SC3 | -18 | 7 | 20.541 |
| SC4 | -25 | 6 | 16.581 |
| SC5 | -34 | 6 | 16.316 |
| A | 2815 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø42 |
| Length | 2815 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.